VESDA Sensepoint XCL – Large Bore Installation Manual
4.8

Troubleshooting

The following flow chart describes the troubleshooting process of VESDA Sensepoint XCL detector during
Calibration and Bump testing:
30
Bump Test
Fail
Pass
Calibrate
Fail
Replace
Sensor Cover /
Calibrate
Pass
Fail
Replace
Gas Sensor /
Calibrate
Fail
Replace Detector
Pass
Detector OK
Pass
VESDA
www.xtralis.com