Quick Start Guide
GFK-2939A

4. Grounding

Proper grounding of this device is essential. The included
ground strap wire must be pressed onto the spade lug
connector on the left side of the ACC402. Cable assembly
IC695CBL002 ties all internal cable shield drains to this
ground.
The frame ground wiring used by both the CPE330 and
ACC402 must be connected to a central ground point.
The green and yellow ground strap wire (see figure 3.1),
which attaches to the spade lug on the side of the
ACC402 base plate, must be connected to the central
ground point.
All ground wires from the host rack or panel must be as
short as possible and terminated at the same grounding
point.
Grounding
Chapter 4
Sep 2019
13