8.3 Description of functions

The description of functions is based on the four main menus of
the CU 352 control unit:

Status

Operation
Alarm
Settings.
The functions apply to all control variants unless otherwise
stated.
8.4 Status (1)
This display is shown when the power is switched on, and it
appears if the buttons of the operating panel remain untouched
for 15 minutes.
E
I
C
D
Fig. 6
Status
Description
No settings can be made in this menu.
The actual value (process value, PV) of the control parameter,
usually the outlet pressure, is shown in the upper right corner (G)
together with the selected setpoint (SP) (H).
The upper half of the display (A) shows a graphic illustration of
the pump system. The selected measuring parameters are shown
with sensor symbol and actual value.
In MPC-E systems where the differential pressure across the
pumps and pump curve data are known, the display shows the
estimated flow rate when the flow rate and speed of the pumps
are within a range where it is possible to estimate the flow rate.
≈ : This indicates that the flow rate is an estimated value.
The estimated flow rate may differ from a measured
value.
In the middle of the display, an information field (I) is shown if any
of the following events occurs:
Limited operation due to standby pump
Proportional-pressure influence active
External setpoint influence active
Alternative setpoint active
Low flow boost active
Pressure relief active
Clock program active
Remote-controlled via GENI (RS-485)
Limited due to reduced operation
Stopped due to low flow.
The lower display half (B) shows the following:
the most recent active alarm, if any, and the fault cause with
the fault code in brackets
F
system status with actual operating mode and control source
G
pump status with actual operating mode.
H
If a fault has occurred, the warning symbol or alarm
symbol is shown in the line (C) together with the
cause and fault code, for instance "Overtemperature
A
(64)".
If the fault is related to one of the pumps, a warning or alarm
symbol is also shown in front of the status line (D) of the pump in
question. At the same time, the pump status indicator (E)
changes colour to either yellow or red as described in the table
B
below. The warning or alarm symbol is shown to the right in the
top line of the display (F). As long as a fault is present, this
symbol is shown in the top line of all displays.
To open a menu line, select the line with [Down] or [Up] and press
[OK].
The display allows you to open status displays showing the
following:
actual alarms
system status
status of each pump.
Description of pump status
Pump status indicator
Rotating, green
Permanently green
Rotating, yellow
Permanently yellow
Permanently red
Description
The pump is running.
The pump is ready (not running).
Warning. The pump is running.
Warning. The pump is ready (not
running).
Alarm. The pump is stopped.
19