07: Bypass voltage range setting
Parameter 2: Set the acceptable high voltage
point and acceptable low voltage point for
Bypass mode by pressing the Down key or
Up key.
HLS: Bypass high voltage point
HLS
26 0
Vac
230-264: setting the high voltage point in
INPUT
parameter 3 from 230Vac to 264Vac. (Default:
264Vac)
LLS: Bypass low voltage point
170-220: setting the low voltage point in
parameter 3 from 170Vac to 220Vac. (Default:
170Vac)
08: Bypass frequency range setting
Parameter 2: Set the acceptable high fre-
quency point and acceptable low frequency
point for Bypass mode by pressing the
Down key or Up key.
HLS
53 0
HLS: Bypass high frequency point
Hz
INPUT
51-55Hz: setting the frequency high loss
point from 51Hz to 55HZ(Default: 53.0Hz).
LLS: Bypass low Frequency point
45-49Hz: setting the frequency low loss point
from 45Hz to 49HZ(Default: 47.0Hz)
09: Programmable outlets enable/disable
Parameter 2: Enable or disable the program-
mable outlets function.
d I S
You may choose the following two options:
ENA: Programmable outlets enable
DIS: Programmable outlets disable (Default)
P1
22
10: Programmable outlets setting
Parameter 2: Set up backup time limits for
programmable outlets.
M
0-999: setting the backup time limits in
999
minutes from 0-999 for programmable
outlets which connect to non-critical
devices on battery mode. (Default: 999).
P1
11: Autonomy limitation setting
Parameter 2: Set up backup time on battery
mode for general outlets.
0-999: setting the backup time in minutes from
0-999 for general outlets on batt. mode.
M
999
DIS: Disable the autonomy limitation and
the backup time will depend on battery
capacity. (Default)
NOTE:
When setting as "0", the backup time
will be only 10 seconds.
12: Battery total AH setting
Parameter 2: Set up the battery total AH of
the UPS.
7-999: setting the battery total capacity
from 7-999 in AH. Please set the correct
battery total capacity if external battery
bank is connected.
bAH
7
EXAMPLE: if you use Balder 1500
together with one battery cabinet with 6
pcs of 12V7Ah batteries (two strings of 3
batteries), total battery AH setting will be:
9AH (UPS battery string capacity) + 2x7AH
(2 strings of 7Ah batteries inside battery
cabinet) = 23AH
13: Maximum charger current setting
If you use external battery pack please set
the appropriate charging current based
CHA
on battery capacity used. Please use the
following table as reference:
23