5.5 UPS settings
1
2
888 888
NOTE!
Most parameters can be set only in bypass/standby mode; please set the UPS
to bypass/standby mode (see section 5.1) and then change parameters.
There are two parameters to set up the UPS.
Parameter 1:
For program alternatives. Refer to the table below.
Parameter 2&3:
The settings options or values for each program.
Interface
Settings
01: Output voltage settings
Parameter 2: Output voltage:
200: presents output voltage is 200Vac
208: present output voltage is 208Vac
220: present output voltage is 220Vac
23 0
Vac
230: present output voltage is 230Vac
OUTPUT
240: present output voltage is 240Vac
NOTE:
Derate capacity to 80% when the output
voltage is adjusted to 200VAC/208VAC.
02: Frequency Converter enable/disable
Parameter 2: Enable or disable converter
mode.
You may choose the following two options:
CF ENA
CF ENA: converter mode enable
CF DIS: converter mode disable (Default)
NOTE:
Derate capacity to 80% when Frequency
Converter mode is enabled.
20
3
03: Output frequency settings
Parameter 2: You may set the initial frequency
on battery mode:
BAT 50: presents output frequency of 50Hz
BAT 60: presents output frequency of 60Hz
CF 5 00
Hz
If converter mode is enabled, you may choose
OUTPUT
the following output frequency:
CF 50: present output frequency is 50Hz
CF 60: present output frequency is 60Hz
04: ECO enable/disable
Parameter 2: Enable or disable ECO function.
You may choose the following two options:
ENA
ENA: ECO mode enable
DIS: ECO mode disable (Default)
05: ECO voltage range setting
Parameter 2: Set the acceptable high
voltage point and low voltage point for ECO
mode by pressing Down key or Up key.
HLS: High loss voltage in ECO mode in
parameter 2.
The setting range in parameter 3 is from +7V
Vac
HLS
23 0
to +24V of the nominal voltage. (Default:
INPUT
+12V)
LLS: Low loss voltage in ECO mode in
parameter 2.
The setting range in parameter 3 is from -7V
to -24V of the nominal voltage.
(Default: -12V)
06: Bypass enable/disable when UPS is off
Parameter 2: Enable or disable Bypass
function. You may choose the following two
ENA
options:
ENA: Bypass enable
DIS: Bypass disable (Default)