3. Open the front-side door of the enclosure as shown below (left), and mount the backside of
the enclosure to the wall or surface using field-supplied fixing screws inserted through the
previously prepared holes at each corner as shown below (right).
4. Screw the cable glands, which are supplied loose, into the openings at the bottom of the
enclosure.
ATTENTION
!
Signal errors through noise from live power supply cords
Power supply cords can generate noise, which may cause signal errors, if they are run in close
proximity to any extra-low voltage control wiring.
► Keep 230 V AC power supply wiring apart from the extra-low voltage control wiring for
sensors etc.
► Route 230 V AC power supply wiring through different cable glands than the extra-low
voltage control wiring.
5. Insert the wiring from below the enclosure through the screwed cable glands and connect the
wires to the terminal block as required.
6. After having finished wiring of the AHU Kit, close the front-side door of the enclosure and
proceed with the installation of all other required system components (see →
expansion valve, p. 51
be ready for matching the outdoor unit capacity with AHU Kit capacity (see →
outdoor unit capacity with AHU Kit capacity, p.
50
and →
4.3 Installation of thermistors, p.
56).