Electrical Wiring
Two suitable methods will be explained in the following sections. All wiring diagrams are just exam-
ples. It is not necessary to build the electric circuit with 230 V AC. Any other suitable lower voltage
being available on site may be used as well.
Method A: For standard fan control
For systems with standard fan control, the external signal lines can simply be connected to the
contacts provided by the AHU Kit. The following installation requirements must be observed.
For MAH2/PAH2 generation models
5
For PAH3 generation models
96
● Blower signal output: terminals D4 (IZ-5) and D5 (IZ-3).
Blower protection input: terminals D6 (OP3) and D7 (2Z-7).
● Blower signal and blower protection lines must be routed through left wiring port below
the terminal board.
● Blower signal output: terminals F1 (X2.1) and F2 (X2.2).
● Max. 8 A / 230 V AC, potential free
Detail view
10P Connector / Section D
1
2 3 4 5
6 7
4 5
6 7
Blower signal output Blower protection
Detail view
1
Blower signal output
AHU Kit – Installation Instructions – 09/2021
8 9 10
2