Panasonic PAW-160MAH2L Installation Instructions Manual page 106

Air handling unit kit
Table of Contents

Advertisement

Control
4. Press the
5. Use the
6. Confirm the complete parametrization by pressing and holding the
9
Parametrization is now complete. The PV and SV displays have returned to showing the current
temperature and the set temperature values respectively.
Switching from 0–10 V to 2–10 V output signals
The voltage range for the output signals on terminals 6–7 is factory-set to 0–10 V.
Switching the voltage range from 0–10 V to 2–10 V is possible. However, Panasonic recommends
to keep the factory setting.
To switch from 0–10 V to 2–10 V output signals, perform the following steps:
1. Press and hold the
7
2. Use the
3. Confirm the new setting by pressing the
4. Press the
5. Use the
106
S S E E T T
button repeatedly to select the entry "PSL".
S S E E T T
TR-16e
repeatedly
and
buttons to change the value to either "0" (= factory setting) for „heating
mode" or "1" for „cooling mode".
S S E E T T
TR-16e
approximatedly 3 seconds.
S S E E T T
TR-16e
1 x for 3 sec.
S S E E T T
and
S S E E T T
TR-16e
1 x 2 buttons for 5 sec.
The PV display shows "PAS", while the current setting ("0") in the SV display is blinking.
Note: After 30 seconds of idleness, the display automatically returns from parametrization view
to normal view.
,
and
S S E E T T
TR-16e
S S E E T T
TR-16e
1 x briefly
The PV display now shows "nun", while the SV display now shows "3".
S S E E T T
button repeatedly to select the entry "AO".
S S E E T T
TR-16e
repeatedly
and
buttons to change the value to either "1" for "output 2 ... 10V" or "2"
(= factory setting) for „output 0 ... 10V".
S S E E T T
TR-16e
buttons jointly for approximately 5 seconds.
buttons to change the value to "–72" (minus 72).
S S E E T T
button.
S S E E T T
button for
AHU Kit – Installation Instructions – 09/2021