Air handling unit kit
Table of Contents

Advertisement

Stranded wire
1. Cut the wire end with cutting pliers, then strip the insulation to expose the stranded wiring about
10 mm and tightly twist the wire ends.
2. Using a flat-blade screwdriver, loosen the terminal screw(s) on the terminal plate.
3. Attach a wire-end sleeve to each stripped wire end using a crimping tool.
4. Place the wire-end sleeve into the socket on the connector and replace and tighten the removed
terminal screw using a flat-blade screwdriver.
Wire-end sleeve
Wire
Shielded wire
1. Remove cable sheath not to scratch braided shield.
2. Unbraid the braided shield carefully and twist the unbraided shield wires tightly together.
Insulate the shield wires by covering them with an insulation tube or wrapping insulation tape
around wire.
3. Remove insulation of signal wire.
4. Attach wire-end sleeves to the signal wires and the shield wires insulated in step 2 using a
crimping tool.
5. Connect the shield for the inter-unit control wiring to ground.
AHU Kit – Installation Instructions – 09/2021
Wire-end
sleeve
Screw
Special washer
Terminal plate
Insulation tape
Shield mesh
Insulation tape
Shield mesh
Wire-end sleeve
Screw and special washer
Wire
Wire-end sleeve
Electrical Wiring