Panasonic PAW-160MAH2L Installation Instructions Manual page 48

Air handling unit kit
Table of Contents

Advertisement

Installation
3. Loosen the 4 screws in the corners of the enclosure and remove the cover from the enclosure.
4. Mount the backside of the enclosure to the wall or surface using field-supplied fixing screws
inserted through the previously prepared holes at each corner.
ATTENTION
!
Signal errors through noise from live power supply cords
Power supply cords can generate noise, which may cause signal errors, if they are run in close
proximity to any extra-low voltage control wiring.
► Keep 230 V AC power supply wiring apart from the extra-low voltage control wiring for
sensors etc.
► Route 230 V AC power supply wiring through different cable glands than the extra-low
voltage control wiring.
5. Insert the wiring preferably from below the enclosure through the screwed cable glands and
connect the wires to each of the 6 connectors as required.
After having finished wiring and applying power to the AHU Kit, auto-addressing can be
performed and the parameters of the thermostat (advanced version only) can be set.
48
AHU Kit – Installation Instructions – 09/2021