Panasonic PAW-160MAH2L Installation Instructions Manual page 12

Air handling unit kit
Table of Contents

Advertisement

General information and safety notes
Density limit diagrams
The following diagrams roughly demonstrate the relation between the amount of refrigerant
charged for the relevant R32 PACi or PACi NX outdoor units ([mc]) and the required minimum
installation space floor area.
AHU units
For the AHU units, the density limit diagram shows three different "Density Limit Lines", where each
line applies to a different AHU unit installation height and installation orientation (horizontal/vertical)
1
as follows:
Installation height of indoor unit (h
h
0
1.8 m ≤ h
h
0
In the ceiling
12
≥ 2.2 m
< 2.2 m
0
< 1.8 m
Indoor unit
h
≥ 2.2 m
0
550
500
450
400
350
300
250
200
150
100
50
0
0.0
0.5
1.0
1.5
2.0
1.22
)
Indoor unit type
0
AHU unit (horizontal installation)
AHU unit (horizontal installation)
AHU unit (vertical installation)
In a false ceiling with change in ceiling
height
Indoor unit
1.8 m ≤ h
< 2.2 m
0
2.5
3.0
3.5
4.0
4.5
[m
]: refrigerant charge (kg) of the outdoor unit
c
In the ceiling
Indoor unit
0.25 m ≤ h
< 1.8 m
0
5.0
5.5
6.0
6.5
7.0
AHU Kit – Installation Instructions – 09/2021
Density limit
line
Line 1
Line 2
Line 3
In the room
Line 3
Line 2
Line 1
7.5
8.0
8.5
7.90