4.3.2 Installation of thermistor on liquid pipe

Mount "E1" thermistor to the liquid pipe of the AHU heat exchanger according to the following
instructions.
1. Attach the liquid pipe thermistor to the liquid pipe located in the lowest position after the
distributor in the heat exchanger.
2. Cover the thermistor and pipe with aluminum tape.
3. Cover the aluminum tape with thermal insulation.
4. Fix thermal insulation and wiring with two bands. Then, run the wire downwards in a loop, to
avoid putting tension to it.

4.3.3 Installation of thermistor on heat exchanger pipe middle

Installation of thermistor on heat exchanger pipe middle – PACi and PACi NX
systems
NX
Mount "E2" thermistor to the heat exchanger pipe middle according to the following instructions.
1. Attach the heat exchanger pipe middle thermistor in the middle of each pass-line (pipe) in the
heat exchanger.