See the recommended procedure as described in
during commissioning" on
page 20.
3.2.2

Third-party tank requirements

In case of a third-party tank, the tank shall adhere to the following
requirements:
▪ The heat exchanger coil of the tank is ≥1.8 m².
▪ The tank thermistor must be located above the heat exchanger
coil.
▪ The booster heater must be located above the heat exchanger
coil.
NOTICE
Performance data for third-party tanks CANNOT be
provided nor guaranteed.
NOTICE
When connecting a third-party tank, configure as EKHWS
tank type.
3.3

Preparing electrical wiring

3.3.1
Overview of electrical connections for
external and internal actuators
Item
Description
Outdoor unit and indoor unit power supply
1
Power supply for
outdoor unit
2
Power supply and
interconnection cable to
indoor unit
3
Power supply for
backup heater
4
Preferential kWh rate
power supply (voltage
free contact)
5
Normal kWh rate power
supply
Optional equipment
6
3‑way valve
7
Power supply for
booster heater and
thermal protection
(from indoor unit)
8
Power supply for
booster heater (to
indoor unit)
9
Domestic hot water
tank thermistor
10
User interface used as
room thermostat
11
Room thermostat
12
Outdoor ambient
temperature sensor
13
Indoor ambient
temperature sensor
14
Heat pump convector
Field supplied components
15
Shut-off valve
EABH/X16DA+9W
Daikin Altherma – Low temperature split
4P556066-1 – 2018.10
"6.2  Checklist
Wires
Maximum
running
current
(a)
2+GND
(g)
3
See table below. —
(e)
2
2
6.3 A
(b)
3
100 mA
(c)
4+GND
2+GND
13 A
(d)
2
(f)
2
(b)
3 or 4
100 mA
(b)
2
(b)
2
(b)
2
100 mA
(b)
2
100 mA
Item
Description
16
Electricity meter
17
Domestic hot water
pump
18
Alarm output
19
Changeover to external
heat source control
20
Space cool/heat
operation control
21
Power consumption
digital inputs
22
Safety thermostat
(a)
Refer to name plate on outdoor unit.
(b)
Minimum cable section 0.75 mm².
(c)
Cable section 2.5 mm².
(d)
The thermistor and connection wire (12 m) are delivered
with the domestic hot water tank.
(e)
Cable section 0.75 mm² till 1.25 mm²; maximum length:
50 m. Voltage-free contact shall ensure the minimum
applicable load of 15 V DC, 10 mA.
(f)
Cable section 0.75 mm² till 1.25 mm²; maximum length:
500 m. Applicable for both single user interface and dual
user interface connection.
(g)
Cable section 1.5 mm².
NOTICE
More technical specifications of the different connections
are indicated on the inside of the indoor unit.
Backup heater
Power supply
type
*6V
1N~ 230 V (6V)
3~ 230 V (6T1)
*9W
3N~ 400 V
4

Installation

4.1

Opening the units

4.1.1

To open the indoor unit

1 Remove the front panel.
2
2 If you have to connect electrical wiring, remove the switch box
cover.
4 Installation
Wires
Maximum
running
current
(b)
2 (per meter)
(b)
2
(b)
2
(b)
2
(b)
2
(b)
2 (per input
signal)
(e)
2
Required number of
conductors
2+GND
3+GND
4+GND
2
1
3
Installation manual
5