NOTICE
Make sure to select and install the safety thermostat
according to the applicable legislation.
In any case, to prevent unnecessary tripping of the safety
thermostat, it is recommended that ...
▪ ... the safety thermostat is automatically resettable.
▪ ... the safety thermostat has a maximum temperature
variation rate of 2°C/min.
▪ ... there is a minimum distance of 2  m between the
safety thermostat and the motorised 3‑way valve
delivered with the domestic hot water tank.
INFORMATION
After it is installed, do NOT forget to configure the safety
thermostat. Without configuration, the indoor unit will
ignore the safety thermostat contact.
INFORMATION
The preferential kWh rate power supply contact is
connected to the same terminals (X5M/9+10) as the safety
thermostat. It is only possible for the system to have
EITHER preferential kWh rate power supply OR a safety
thermostat.
4.5
Finishing the indoor unit
installation
4.5.1

To close the indoor unit

1 Reinstall the user interface panel.
2 Reinstall the switch box cover and close the switch box.
3 Reinstall the front panel.
NOTICE
When closing the indoor unit cover, make sure that the
tightening torque does NOT exceed 4.1 N•m.
5

Configuration

5.1

Overview: Configuration

This chapter describes what you have to do and know to configure
the system after it is installed.
NOTICE
The explanation about the configuration in this chapter
gives you ONLY basic explanations. For more detailed
explanation and background information, see the installer
reference guide.
Why
If you do NOT configure the system correctly, it might NOT work as
expected. The configuration influences the following:
▪ The calculations of the software
▪ What you can see on and do with the user interface
How
You can configure the system via the user interface.
▪ First time – Configuration wizard. When you turn ON the user
interface for the first time (via the indoor unit), the configuration
wizard starts to help you configure the system.
EABH/X16DA+9W
Daikin Altherma – Low temperature split
4P556066-1 – 2018.10
▪ Restart the configuration wizard. If the system is already
configured, you can restart the configuration wizard. To restart the
configuration wizard, go to Installer settings > Configuration
wizard. To access Installer settings, see
most used commands" on
page 13.
▪ Afterwards. If necessary, you can make changes to the
configuration in the menu structure or the overview settings.
INFORMATION
When the configuration wizard is finished, the user
interface will show an overview screen and request to
confirm. When confirmed, the system will restart and the
home screen will be displayed.
Accessing settings – Legend for tables
You can access the installer settings using two different methods.
However, NOT all settings are accessible via both methods. If so,
the corresponding table columns in this chapter are set to N/A (not
applicable).
Method
Accessing settings via the breadcrumb in the
menu structure. To enable breadcrumbs,
press the
button in the home screen.
Accessing settings via the code in the
overview field settings.
See also:
"To access the installer settings" on page 13
"5.4 Menu structure: Overview installer settings" on page 19
5.1.1

To access the most used commands

To change the user permission level
You can change the user permission level as follows:
1 Go to [B]: User profile.
2 Enter the applicable code for the user permission.
▪ Move the cursor from left to right.
▪ Browse through the list of digits and change the
selected digit.
▪ Confirm the pincode and proceed.
Installer pin code
The Installer pin code is 5678. Additional menu items and installer
settings are now available.
Installer
5678
Advanced user pin code
The Advanced user pin code is 1234. Additional menu items for the
user are now visible.
User pin code
The User pin code is 0000.
To access the installer settings
1 Set the user permission level to Installer.
2 Go to [9]: Installer settings.
To modify an overview setting
Example: Modify [1‑01] from 15 to 20.
5 Configuration
"5.1.1  To access the
Column in tables
#
Code
Installation manual
13