Configuration wizard: Time and date ......14 Daikin website (publicly accessible). 5.2.3 Configuration wizard: System ........14 ▪ The full set of latest technical data is available on the Daikin 5.2.4 Configuration wizard: Backup heater ......15 extranet (authentication required).
In case the minimum flow rate cannot be reached, a flow error 7H will be generated (no heating or operation). See the installer reference guide for more information. Minimum required flow rate 20 l/min Installation manual EABH/X16DA+9W Daikin Altherma – Low temperature split 4P556066-1 – 2018.10...
Indoor ambient temperature sensor Heat pump convector 100 mA 2 If you have to connect electrical wiring, remove the switch box Field supplied components cover. Shut-off valve 100 mA EABH/X16DA+9W Installation manual Daikin Altherma – Low temperature split 4P556066-1 – 2018.10...
▪ Slide the bracket on the back of the unit over the wall bracket. Make sure the unit is fixed properly. Installation manual EABH/X16DA+9W Daikin Altherma – Low temperature split 4P556066-1 – 2018.10...
"6.2.1 To check the minimum flow rate" on page 20. NOTICE Install air purge valves at all local high points. Drain pan connector It is recommended to use a tundish to collect the water. EABH/X16DA+9W Installation manual Daikin Altherma – Low temperature split 4P556066-1 – 2018.10...
If glycol is present in the system, setting [E-0D] must be set to 1. If the glycol setting is NOT set correctly, the liquid inside the piping can freeze. Freeze protection by freeze protection valves Installation manual EABH/X16DA+9W Daikin Altherma – Low temperature split 4P556066-1 – 2018.10...
4.4.3 To connect the main power supply 2 Route the wiring as follows: 1 Connect the main power supply. In case of normal kWh rate power supply EABH/X16DA+9W Installation manual Daikin Altherma – Low temperature split 4P556066-1 – 2018.10...
EITHER preferential kWh rate power supply OR a safety thermostat. Q1DI Factory-mounted cable connected to the backup heater contactor inside the switch box (K5M for *6V and *9W models) Field wiring (see table below) Installation manual EABH/X16DA+9W Daikin Altherma – Low temperature split 4P556066-1 – 2018.10...
Safety contactor (in the switch box) Q1DI Earth leakage circuit breaker (field supply) Switch box 2 Fix the cable with cable ties to the cable tie mountings. Terminal (field supply) EABH/X16DA+9W Installation manual Daikin Altherma – Low temperature split 4P556066-1 – 2018.10...
2 Fix the cable with cable ties to the cable tie mountings. 1 Connect the changeover to external heat source cable to the appropriate terminals as shown in the illustration below. Installation manual EABH/X16DA+9W Daikin Altherma – Low temperature split 4P556066-1 – 2018.10...
(via the indoor unit), the configuration To modify an overview setting wizard starts to help you configure the system. Example: Modify [1‑01] from 15 to 20. EABH/X16DA+9W Installation manual Daikin Altherma – Low temperature split 4P556066-1 – 2018.10...
24 hours. If you want to change these settings, you can do this in the menu structure (User settings > Time/date) once the unit is initialised. Installation manual EABH/X16DA+9W Daikin Altherma – Low temperature split 4P556066-1 – 2018.10...
If [4‑0A]=3 and emergency mode is active, the power system in this way could cause damage to the heat usage of the backup heater is maximal and equal to emitters. 2×[6‑03]+[6‑04]. EABH/X16DA+9W Installation manual Daikin Altherma – Low temperature split 4P556066-1 – 2018.10...
50°C, temperature and/or heating or cooling demand Daikin recommends NOT to disable the backup heater of the room. second step because it will have a big impact on the...
Additionally, a storage stop can be programmed. This feature puts a Confirm changes and proceed. stop to tank heating even if the setpoint has NOT been reached. Only program a storage stop when tank heating is absolutely undesirable. EABH/X16DA+9W Installation manual Daikin Altherma – Low temperature split 4P556066-1 – 2018.10...
ON/OFF condition. 5.3.2 Additional zone Thermostat type Only applicable in external room thermostat control. For more info about the functionality, see "5.3.1 Main zone" on page 18. Installation manual EABH/X16DA+9W Daikin Altherma – Low temperature split 4P556066-1 – 2018.10...
Solar kit settings are shown but are NOT applicable for this unit. Settings shall NOT be used or changed. INFORMATION Depending on the selected installer settings and unit type, settings will be visible/invisible. EABH/X16DA+9W Installation manual Daikin Altherma – Low temperature split 4P556066-1 – 2018.10...
To stop the air purge manually: — The correct pipe size is installed and the pipes are 1 Go to Stop air purge. properly insulated. 2 Select OK to confirm. Installation manual EABH/X16DA+9W Daikin Altherma – Low temperature split 4P556066-1 – 2018.10...
▪ Shut off valve test ▪ Diverter valve test ▪ Bivalent signal test ▪ Alarm output test ▪ C/H signal test ▪ DHW pump test EABH/X16DA+9W Installation manual Daikin Altherma – Low temperature split 4P556066-1 – 2018.10...
8 Technical data Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin Business Portal (authentication required). Piping diagram: Indoor unit...
Page 24
Only for wired On/OFF thermostat thermostat Electrical meters Electrical meters Only for wireless On/OFF Only for wireless On/OFF For safety thermostat For safety thermostat thermostat thermostat Inrush Inrush current Installation manual EABH/X16DA+9W Daikin Altherma – Low temperature split 4P556066-1 – 2018.10...
Page 25
2 core Power limitation 2x0.75 A8P: X801M: 4-5 demand input 4 X5M: 11-12 A14P: P1-P2 user interface signal communication 2 core 2x0.75 A13P: P1-P2 LAN adapter communication 4D120628 EABH/X16DA+9W Installation manual Daikin Altherma – Low temperature split 4P556066-1 – 2018.10...