To finish the outdoor unit installation ......40 6.2.1 Installation site requirements of the outdoor unit ..21 Finishing the indoor unit installation ........... 40 Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
Indicates a situation that could result in minor or moderate 12.3.9 Symptom: The pressure at the tapping point is injury. temporarily unusually high .......... 79 EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
▪ In places where there is a risk of fire due to the leakage of comply with applicable legislation (on top of the flammable gases (example: thinner or gasoline), carbon fibre, instructions described in the Daikin documentation). ignitable dust. ▪ In places where corrosive gas (example: sulphurous acid gas) is CAUTION produced.
When the refrigerant charging procedure is done or when pausing, close valve refrigerant tank immediately. If the valve is NOT closed immediately, remaining pressure might charge additional refrigerant. Possible consequence: Incorrect refrigerant amount. EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
Daikin website (publicly accessible). to prevent interference. Depending on the radio waves, a distance of 1 metre may not be sufficient. ▪ The full set of latest technical data is available on the Daikin extranet (authentication required). Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma –...
3.2.2 To handle the outdoor unit advance. CAUTION To avoid injury, do NOT touch the air inlet or aluminium fins of the unit. 143 kg EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
4 Re-install the nut (a) of the compressor mounting bolt and tighten to 10.1 N•m of torque. 4× 2× 1× 1× General safety precautions Addendum book for optional equipment Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
PCB and addendum book for optional equipment. Remote indoor sensor (KRCS01-1) By default the internal user interface sensor will be used as room temperature sensor. EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
(modulation). This results in: Benefits ▪ Stable room temperature matching the desired temperature ▪ Wireless. The Daikin external room thermostat is available in a (higher comfort) wireless version. ▪ Less ON/OFF cycles (more quiet, higher comfort and higher ▪...
▪ A shut-off valve (field supply) is installed before the under floor heating to prevent condensation on the floor during cooling operation. Main leaving water temperature zone Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
Page 13
(X2M/35 and X2M/30). The indoor unit will only supply leaving water temperature when there is an actual demand. INFORMATION To increase comfort and performance, Daikin recommends to install the valve kit option EKVKHPC on each heat pump convector. Configuration...
Room 1 Room 2 INFORMATION Main leaving water temperature zone To increase comfort and performance, Daikin recommends Room 3 Remote controller of the heat pump convectors to install the valve kit option EKVKHPC on each heat pump User interface used as room thermostat convector.
▪ Make sure the auxiliary boiler and its integration in the ▪ #: [4.4] system complies with applicable legislation. ▪ Code: [7-02] ▪ Daikin is NOT responsible for incorrect or unsafe In case of heat pump convectors: 1 (1 contact): When the used situations in the auxiliary boiler system.
Example: If the DHW consumption of a family (4 persons) per day is as follows: ▪ 3 showers ▪ 1 bath ▪ 3 sink volumes Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
▪ If energy prices are the same during the day and the night, Domestic hot water OUT Daikin recommends to heat up the DHW tank during the day. Recirculation connection ▪ If energy prices are lower during the night, Daikin recommends ▪...
Example: If you measure a booster heater resistance of 17.1Ω, the capacity of the heater at 230 V is 3100 W. Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
Permanent power limitation is useful to assure a maximum power or current input of the system. In some countries, legislation limits the maximum power consumption for space heating and DHW production. EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
Power limitation is also useful in combination with an energy time), the digital input priority is fixed: DI4 priority>…>DI1. management system. The power or current of the entire Daikin system is limited 5.6.3 Power limitation process dynamically by digital inputs (maximum four steps). Each power The outdoor unit has better efficiency than the electrical heaters.
▪ That is NOT affected by outside air or air draught because of, for example, door opening/closing 6.2.1 Installation site requirements of the ▪ If this is NOT possible, Daikin recommends to connect a remote outdoor unit indoor sensor (option KRCS01-1). INFORMATION ▪...
It is NOT recommended to install the unit in the following places because it may shorten the life of the unit: Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable ▪ Where the voltage fluctuates a lot legislation (for example national gas regulation) and are ▪...
(if equipped) MUST be open. match your system layout. 6.3.1 Water circuit requirements INFORMATION Also read the precautions and requirements in the "General safety precautions" chapter. EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
The total water volume in the water circuit is 250 l. To guarantee proper operation it is recommended to have Actions: a minimum flow of 28 l/min during DHW. EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
At that moment, the outdoor unit compressor will not operate. Whether the power supply is interrupted or not, the wiring to the unit is different. Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
If you remove the user interface panel, also disconnect the cables from the back of the panel to prevent damage. 2 If you have to connect electrical wiring, remove the switch box cover. Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
150 mm of the bottom side of the unit in order to prevent water from getting into the unit and to avoid drain water dripping (see the following figure). EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
To prevent the outdoor unit from falling over In case the unit is installed in places where strong wind can tilt the unit, take following measure: Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
"7.2.3 To open the indoor unit" on page 28. ▪ Fix the unit to the wall with an Ø8 mm screw. ▪ General safety precautions ▪ Preparation EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
INFORMATION Make sure both air purge valves (one on the magnetic filter and one on the backup heater) are open. Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
The types of glycol that can be used depend on whether the system contains a domestic hot water tank: Automatic air intake EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
Flat washer Stranded conductor wire with round crimp-style terminal a Terminal b Screw c Flat washer O Allowed X NOT allowed Power supply cable (high voltage) EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
To connect the main power supply the back of the switch box. 1 Connect the main power supply. In case of normal kWh rate power supply Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
(X5M/9+10) as the safety thermostat. It is only possible for the system to have EITHER preferential kWh rate power supply OR a safety thermostat. EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
X5M/6 and X5M/4; the negative polarity to X5M/5 and X5M/3. 1 Connect the electrical meters cable to the appropriate terminals as shown in the illustration below. Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
1 Connect the space cooling/heating ON/OFF output cable to the appropriate terminals as shown in the illustration below. appropriate terminals as shown in the illustration below. EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
▪ Afterwards. If necessary, you can make changes to the configuration in the menu structure or the overview settings. 1 Insulate and fix the refrigerant piping and interconnection cable as follows: Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
Number of zones [4.4] "8.4.5 Space heating/ change the user permission level" on page 41. cooling" on page 52 2 Go to [9.I]: Installer settings > Overview field Backup heater settings. EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
Leaving water temperature setpoint Home screen g3 Room thermostat type: Main menu screen Lower level screens: ▪ : Daikin user interface used as room c1: Setpoint screen c2: Detailed screen with values thermostat ▪ : External control ▪ Hidden: Leaving water temperature control...
Restriction: Only displayed if a domestic Tank hot water tank is present. Set the domestic hot water tank temperature. EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
The symbol shown here corresponds to the heat emitter for that zone: User defined 1 ▪ : Underfloor heating ▪ : Fan coil unit ▪ : Radiator ▪ : Domestic hot water tank Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
4 Confirm the new name. Settings menu You can set additional settings using the main menu screen and its submenus. The most important settings are presented here. EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
For more detailed information about room frost protection in relation to the applicable unit control method, see the sections below: Leaving water temperature control ([C‑07]=0) Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
10°C. Heating WD curve Set weather-dependent heating for the main zone (if [2.4] = 1 or 2): EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
Page 48
Variable (see [2.B]) (depending on the heat emitter), such situations can be avoided. 1: Fancoil unit Maximum 55°C Variable (see [2.B]) 2: Radiator Maximum 60°C Fixed 8°C Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
Page 49
▪ Else: 3°C~10°C [2.B.2] [1‑0D] Delta T cooling: A minimum temperature difference is required for the good operation of heat emitters in cooling mode. ▪ 3°C~10°C EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
The setpoint mode of the additional zone can be independently set from the setpoint mode of the main zone, see " Main zone" on page 47. Weather-dependent curve Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
Page 51
(= the leaving water temperature zone with the highest leaving water temperature in heating operation and the lowest leaving water temperature in cooling operation) [3.8.1] [9-05] Heating minimum: 15°C~37°C EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
NOT cool down a space. You do NOT In-between. Reversible have to tell the system which space operation mode to use. Example: April, May and September. Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
Page 53
▪ Make sure you set the emitter types for the main zone [2.7] and for the additional zone [3.7] correctly in accordance with the connected emitter. EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
Page 54
▪ g: Pump operation capacity. With this limitation range, delta T is possible and the comfort is guaranteed. The maximum values depend on the unit type: Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
In heating operation, the desired leaving water temperature is locally increased around an outdoor temperature of 0°C.This compensation can be selected when using an absolute or a weather dependent desired temperature (see illustration below). EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
Page 56
The domestic hot water can be prepared in 3 different ways. They differ from each other by the way the desired tank temperature is set and how the unit acts upon it. Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
Page 57
(according to the weather dependent curve), the storage economic INFORMATION and reheat temperature are NOT weather dependent. An AH error occurs if you turn off domestic hot water operation during disinfection. EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
Heat pump OFF temperature (T −[6-01]) HP OFF HP MAX Heat pump ON temperature (T −[6-00]) HP ON HP OFF Domestic hot water temperature Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
Page 59
▪ During the day: Off to ensure the heating/cooling capacity of the system. ▪ However, during the afternoon the baby is sleeping and you want it to be quiet. EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
In menu… You can read out… [8.1] Energy data Produced energy, consumed electricity, and consumed gas [8.2] Malfunction history Malfunction history [8.3] Dealer information Contact/helpdesk number Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
Page 61
50°C, Daikin recommends NOT to disable the backup heater Backup heater second step because it will have a big impact on the...
Page 62
[5‑02]=1. The domestic hot water temperature can be maximum the heat pump OFF temperature. [9.4.4] [4-03] ▪ 1: Booster heater operation is allowed when required. Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
Page 63
Timers for simultaneous space and domestic hot water unattended for longer periods. operation request Code Description [8-02]: Anti-recycle timer [9.5] ▪ 0: Manual ▪ 1: Automatic EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
Page 64
15 minutes. [9.6.7] [8-04] Additional timer: Additional running time for the maximum running time depending on the outdoor temperature [4-02] or [F-01]. Range: 0~95 minutes Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
Page 65
Permitted [9.9.C] [5-0C] Limit 4: 0 kW~20 kW Forced OFF Permitted Permitted Do NOT use 1 or 3. [D‑00] Backup heater Compressor Forced OFF Forced OFF Allowed EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
Page 66
▪ 3 10/kWh: Installed can/will provide the space heating, either the heat pump system or ▪ 4 100/kWh: Installed the auxiliary boiler. ▪ 5 1000/kWh: Installed Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
Page 67
Set them in the menu structure instead ([7.4.5.1], [7.4.5.2], [7.4.5.3], and [7.4.6]). For more information on how to set the energy prices, see the operation manual and the user reference guide. EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
Connection status User profile Operation Room Space heating/cooling Tank Setpoint screen INFORMATION Depending on the selected installer settings and unit type, settings will be visible/invisible. EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
Solar kit settings are shown but are NOT applicable for this unit. Settings shall NOT be used or changed. INFORMATION Depending on the selected installer settings and unit type, settings will be visible/invisible. Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
To check the minimum flow rate 1 Confirm according to the hydraulic configuration — which space heating loops can be closed due to mechanical, electronic, or other valves. EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
Operation menu and turn off Room, Space heating/cooling and Tank operation. Result: The air purge starts. It will stop automatically when air purge cycle is finished. Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
[9‑0D] is NOT applicable. change the user permission level" on page 41. 2 Go to the programming screen [A.4.2]: Commissioning > UFH screed dryout > Program. EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
It is recommended to clean the heat exchanger yearly. A blocked heat exchanger can lead to too low pressure or too high pressure leading to worse performance. Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
ALWAYS take off the magnetic sleeve. ▪ ALWAYS first unscrew the drain cap, and connect a drain hose to the bottom of the water filter, then open the drain valve. EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
To protect the piping connected to the magnetic filter/dirt separator from damage it is recommended to perform this procedure with the magnetic filter/dirt separator removed from the unit. Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
ON and OFF by the utility. DANGER: RISK OF BURNING EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
Reason: Refrigerant might leak into the water circuit, and subsequently into the room when you purge air from the heat emitters or collectors. Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
The disinfection operation was Do NOT stop tank operation stopped manually: [C.3] during disinfection. Operation > Tank was turned off during disinfection. EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
(DHW) overload protection Abnormal increase outlet water OU: Malfunction of position temperature detection sensor Overheating water circuit OU: Malfunction of compressor (thermostat) input (CT) system Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
Page 81
ON. To Indoor/outdoor unit reset the error, press and confirm by pressing communication problem User interface communication problem EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
Make sure that all outside panels, except for the service cover on the electrical component box, are closed while working. Close the lid of the electrical component box firmly before turning on the power. Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
▪ Do NOT apply excessive force to the valve stem. Doing so may Item Tightening torque (N∙m) break the valve body. Service port cap 11.5~13.9 EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
14 Technical data Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin Business Portal (authentication required). 14.1 Service space: Outdoor unit...
Page 90
Electrical meters Electrical meters Only for wireless On/OFF Only for wireless On/OFF For safety thermostat For safety thermostat thermostat thermostat Inrush Inrush current Installer reference guide EPGA11~16DAV3 + EABH/X16DA6V+9W Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
Page 91
Power limitation 2x0.75 A8P: X801M: 4-5 demand input 4 X5M: 11-12 A14P: P1-P2 user interface signal communication 2 core 2x0.75 A13P: P1-P2 LAN adapter communication 4D120628A EPGA11~16DAV3 + EABH/X16DA6V+9W Installer reference guide Daikin Altherma – Low temperature split 4P556069-1 – 2018.10...
Optional equipment Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation. Field supply Equipment NOT made by Daikin that can be combined with product according instructions accompanying documentation.
Page 94
2/10 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value Room └─ Antifrost 1.4.1 [2-06] Activation 0: Disabled 1: Enabled 1.4.2 [2-05] Room setpoint 4~16°C, step: 1°C 8°C └─...
Page 95
3/10 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value Additional zone [2-0D] Emitter type 0: Underfloor heating 1: Fancoil unit 2: Radiator └─ Setpoint range 3.8.1 [9-05] Heating minimum 15~37°C, step: 1°C 25°C...
Page 96
4/10 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value └─ WD curve [0-0B] Leaving water value for high ambient temp. for DHW WD curve. 35~[6-0E]°C, step: 1°C 55°C [0-0C] Leaving water value for low ambient temp.
Page 97
5/10 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value [0-05] Leaving water value for low ambient temp. for LWT add zone cooling WD curve. [9-07]~[9-08]°C, step: 1°C 12°C [0-06] High ambient temp.
Page 98
6/10 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value 9.9.6 [5-07] Limit 3 0~50 A, step: 1 A 50 A 9.9.7 [5-08] Limit 4 0~50 A, step: 1 A 50 A 9.9.8 [5-09]...
Page 99
7/10 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value [1-08] Leaving water value for low ambient temp. for LWT main zone cooling WD curve. [9-03]~[9-02]°C, step: 1°C 22°C [1-09] Leaving water value for high ambient temp.
Page 100
8/10 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value [5-02] Space heating priority. 0: Disabled 1: Enabled [5-03] Space heating priority temperature. -15~35°C, step: 1°C 0°C [5-04] Set point correction for domestic hot water temperature.
Page 101
9/10 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value [9-00] What is the maximum desired LWT for main zone in heating? [2-0C]=2: 37~60, step: 1°C 55°C [2-0C]≠2: 37~55, step: 1°C 55°C [9-01]...
Page 102
10/10 Installer setting at variance with Field settings table default value Breadcrumb Field code Setting name Range, step Date Value Default value [E-04] Is the power saving function available on the outdoor unit? 0: No 1: Yes [E-05] Can the system prepare domestic hot water? 0: No (*3) 1: Yes (*4) [E-06]...