EN - Quick installation and start-up
guide
This guide instructs how to install and start-up the ACS560 drive of all frame sizes (R0...R8).
For complete information, see the drive ACS560 standard control program firmware manual
(3AXD50000044997[English]) and ACS560 drives (0.75 to 160 kW, 1.0 to 215 hp) hardware
manual (3AXD50000044998[English]).

General considerations

Obey the safety instructions
WARNING! Obey these instructions. If you ignore them, injury or death, or damage
to the equipment can occur.
If you are not a qualified electrician, do not do electrical installation work.
Do not work on the drive, motor cable or motor when main power is applied.
If the drive is already connected to the input power, wait for 5 minutes after
disconnecting the input power.
Do not work on the control cables when power is applied to the drive or to the
external control circuits.
Use the lifting eyes of the drive when you lift the drive. Do not tilt the drive.
The drive is heavy and its center of gravity is high. An overturning drive can
cause physical injury.
Make sure that debris from borings and grindings does not enter the drive
when installing.
Make sure that the floor below the drive and the wall where the drive is installed
are non-flammable.
Reform the capacitors
Reform the capacitors if the drive is stored for a year or more.
The manufacturing date is on the type designation label which is attached to the drive. The
serial number format MYYWWRXXXX represents the month, year and the week.
YY: 13, 14, 15, ... for 2013, 2014, 2015, ...
WW: 01, 02, 03, ... for week 1, week 2, week 3, ...
For information on reforming the capacitors, see Converter module capacitor reforming
instructions (3BFE64059629 [English]).
Select the power cables
Size the power cables according to local regulations to carry the nominal current given on
the type designation label of your drive. See
Ensure the cooling
The maximum ambient temperature without derating is:
50 °C (+122 °F) for R0...R2 frames

EN - Quick installation and start-up guide 3

Ratings (page
99).