ABB ACS560 Quick Installation And Start-Up Manual page 101

Standard control program
Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

Drive type
Minimum
ACS560
short cir-
cuit cur-
1)
rent
A
09A4-4
128
12A6-4
200
017A-4
256
025A-4
320
033A-4
320
039A-4
400
046A-4
500
062A-4
800
073A-4
1000
088A-4
1000
106A-4
1300
145A-4
1700
169A-4
3300
206A-4
5500
246A-4
6400
293A-4
7800
1) minimum short-circuit current of the device
gR fuses
Drive type
Minimum
ACS560-
short circuit
1)
current
A
3-phase UN = 380...480 V
02A6-4
48
03A3-4
48
04A0-4
80
05A6-4
80
07A2-4
128
09A4-4
128
12A6-4
200
017A-4
256
025A-4
400
033A-4
170
039A-4
170
046A-4
280
062A-4
380
073A-4
480
088A-4
480
Input cur-
rent
Rated cur-
rent I
N
A
A
15.0
16
20.2
25
27.2
32
40.0
50
33.0
40
39.0
50
45.0
63
62.0
80
73.0
100
88.0
100
106.0
125
145.0
160
169.0
250
206.0
315
246.0
355
293.0
425
1300000
Input cur-
rent
Rated cur-
rent I
N
A
A
4.2
25
5.3
25
6.4
32
9.0
32
11.5
40
15.0
40
20.2
50
27.2
63
40.0
80
32.0
63
38.0
63
45.0
80
62
100
73
125
88
160
gG (IEC 60269)
2
I
t
Rated
ABB designa-
voltage
tion type
2
A
s
V
740
500
OFAF000H16
2500
500
OFAF000H25
4500
500
OFAF000H32
15500
500
OFAF000H50
7700
500
OFAF000H40
16000
500
OFAF000H50
20100
500
OFAF000H63
37500
500
OFAF000H80
65000
500
OFAF000H100
65000
500
OFAF000H100
103000
500
OFAF000H125
185000
500
OFAF000H160
600000
500
OFAF000H250
710000
500
OFAF000H315
920000
500
OFAF000H355
500
OFAF000H425
gG (IEC 60269)
2
I
t
Rated
ABB desig-
voltage
nation type
2
A
s
V
125
690
170M2694
125
690
170M2694
275
690
170M2695
275
690
170M2695
490
690
170M2696
490
690
170M2696
1000
690
170M2697
1800
690
170M2698
3600
690
170M2699
1450
690
170M1565
1450
690
170M1565
2550
690
170M1566
4650
690
170M1567
8500
690
170M1568
16000
690
170M1569
Technical data 101
IEC 60269
size
000
000
000
000
000
000
EN
000
HI
000
000
000
00
00
0
1
1
2
IEC 60269
size
00
00
00
00
00
00
00
00
00
000
000
000
000
000
000