Operating the device
5.5 "t" menu
5.5.1 Time configuration
Display
Setting value
Range
FAC
t
0 ... 10
0
ton
0 ... 99
0
toff
0 ... 99
0
test
OFF / 1 / 24
24
FAC = Factory settings; Cs = Customer settings
5.6 "SEt" menu
5.6.1 Function configuration
Display
Activation
Setting value
FAC
Cs
Range
off
0 . . . 999
nEt
on
S.Ct
on
FAC
SYS
FAC = Factory settings; Cs = Customer settings
18
Description
Cs
s Start-up delay during device start
s Response delay K1 and K2
s Delay on release K1 and K2
h Repetition time device test
Description
FAC
Cs
0
Password for parameter setting
Test of the system connection dur-
ing device test
Device test during device start
Restore factory settings
For Bender service only
Operating the device
5.7 Measured value display and history memory
R
is continuously indicated on the display (standard display). All other measured value
F
displays switch to the standard display after a maximum of 5 min. The pulse symbol indi-
cates a current measured value. If this symbol does not appear, the measurement is still
running and the latest valid measured value will be displayed. The symbols "<" or ">" will
be displayed additionally to the measured value when a response value has been
reached or violated, or the measured value is below or exceeds the measuring range.
HiS
Display
Insulation resistance
±R
kΩ
1 kΩ ... 4 MΩ
System leakage capacitance
μF
0
μF
C
No update when R
Nominal system voltage L1 - L2
~ ± U L1 L2 = V
0 V
RMS
Residual voltage L1/+ - PE
±U L1
V
=
0 V
DC
Residual voltage L2/- - PE
±U L2
V
=
0 V
DC
Fault location in %
±R
%
-100 % ...+100 %
Insulation resistance
1 kΩ ... 4 MΩ
R
U R = kΩ
UGF
tion faults and can be used as a trend indicator with
short measuring times.
:
The measured value is indicated in the history memory.
Description
R
F
Resolution 1 kΩ
C
e
μF
μF
... 105
Resolution 1
is < 10 kΩ.
F
U
n
... 500 V
Resolution 1 V
RMS
RMS
U
L1e
... ±500 V
Resolution 1 V
DC
U
L2e
... ±500 V
Resolution 1 V
DC
R
UGF
Resolution 1 kΩ
is an approximate value for asymmetrical insula-
isoES425_D00214_00_M_XXEN/01.2019
DC
DC
Need help?
Do you have a question about the ISOMETER isoES425 and is the answer not in the manual?
Questions and answers