GEM 566 Series Operating Instructions Manual page 33

Motorized control valve
Table of Contents

Advertisement

Description of parameter values
Index name
Function digital inputs
www.gemu-group.com
Parameter
Values
Input 1
0
1
2
3
4
Input 2
0
1
2
3
4
(Off) Input without function.
(Open) In case of the corresponding signal, the actuator
moves in the OPEN direction. If the other input (Digital Input
2) is configured as "Close", the actuator stops when the in-
puts are not actuated. If the other input is not configured as
"Close", the actuator moves independently in the CLOSED dir-
ection when the "Open" input is not actuated.
(Close) In case of the corresponding signal, the actuator
moves in the CLOSED direction. If the other input (Digital In-
put 2) is configured as "Open", the actuator stops when the
inputs are not actuated. If the other input is not configured as
"Open", the actuator moves independently in the OPEN direc-
tion when the "Close" input is not actuated.
(Safe/On) Safety position of the device is triggered. The
device operates normally if the signal is active. If there is no
signal, the device moves into the safety position. The safety
position is defined by the parameter Error Action (index 0x4F
(see "Error Action'").
(Init) Input can be used as an initialization input.
(Off) Input without function.
(Open) In case of the corresponding signal, the actuator
moves in the OPEN direction. If the other input (Digital Input
1) is configured as "Close", the actuator stops when the in-
puts are not actuated. If the other input is not configured as
"Close", the actuator moves independently in the CLOSED dir-
ection when the "Open" input is not actuated.
(Close) In case of the corresponding signal, the actuator
moves in the CLOSED direction. If the other input (Digital In-
put 1) is configured as "Open", the actuator stops when the
inputs are not actuated. If the other input is not configured as
"Open", the actuator moves independently in the OPEN direc-
tion when the "Close" input is not actuated.
(Safe/On) Safety position of the device is triggered. The
device operates normally if the signal is active. If there is no
signal, the device moves into the safety position. The safety
position is defined by the parameter Error Action (index 0x4F
(see "Error Action'").
(Init) Input can be used as an initialization input.
33 / 57
12 Specific data IO-Link (pin 6)
Description
GEMÜ 566
Code S0

Advertisement