Index Sub-
Access
Index
rights
0x4F
1
R/W
2
R/W
0x50
1
R/W
2
R/W
3
R/W
4
R/W
0x51
1
R/W
2
R/W
3
RO
4
RO
0x53
1
RO
2
RO
3
RO
0x55
1
RO
2
RO
0x60
1
RO
2
RO
3
RO
4
RO
0x62
1
RO
2
RO
0x90
2
R/W
www.gemu-group.com
Index name
Error action
Error action
Basic settings
Inversion of LED col-
On site initialization
Operating mode
IO-Link process data Activate/deactivate
Actuator position
Open request
feedback
Close request
Initialized positions
Calibrated positions
Analog values
Potentiometer
Supply voltage
Temperature
Set value (W)
Operating times
Drive sets
Parameter
Function
Set safety position
Error time
Determine time
from error detection
to error message
Activate / deactiv-
ours
ate inversion of
LEDs
Activate / deactiv-
ate on site initializa-
tion
Operating mode
change-over (posi-
tioner; ON/OFF)
use of IO-Link pro-
cess data
Request valve posi-
tion OPEN
Request valve posi-
tion CLOSED
Open real
Real valve position
OPEN
Close real
Real valve position
CLOSED
Open
Analog value valve
position OPEN
Close
Analogue value
valve position
CLOSED
Stroke
Read out the analog
value for stroke (dif-
ference between
OPEN and CLOSED).
Max.
OPEN end position
Min.
CLOSED end posi-
tion
Analog value poten-
tiometer
Analog value supply
voltage
Analog value tem-
perature sensor
Analog value set
value signal
Open
Operating time
OPEN
Close
Operating time
CLOSE
Force
Force, dependent on
valve used
25 / 57
12 Specific data IO-Link (pin 6)
Factory
Setting options
settings
2
0 → Hold
1 → Open
2 → Close
1 (0.1s)
1 ... 1000
(0.1s ... 100s)
0
0 → Standard
1 → Inversed
0
0 → Enabled
1 → Disabled
0
0 → Positioner
1 → On/Off
0
0 → Disabled
1 → Enabled
900
30 ... 970
(90.0%)
(3.0 ... 97.0%)
100
30 ... 970
(10.0%)
(3.0 ... 97.0%)
0 ... 4095
0 ... 4095
0 ... 4095
0 ... 4095
0 ... 4095
0 ... 4095
0 ... 4095
0 ... 4095
0 ... 4095
0 ... 4095
0 ... 4095
0
0 to 255
(0 to 25.5s)
0
0 to 255
(0 to 25.5s)
1 ... 6
GEMÜ 566
Code S0