ABB MagMaster Configuration Manual page 23

Electromagnetic flowmeter
Hide thumbs Also See for MagMaster:
Table of Contents

Advertisement

...B1.2 Description of Parameters
Main Menu
Alm
8 >
Sub-menus
8
Alm No1
1 >
Alm No2
2 >
Alm Trip
3 >
Alm Quit
Q >
1
Alm No 1 Idle
1> 0
Alm No 1 En
2> 1
Alm No 1 Fault
3> 1
Alm No 1 Fwd
4> 1
Alm No 1 Rev
5> 0
Alm No 1 Cutoff
6> 1
Alm No 1 Mtsnsr
7> 0
Alm No 1 Hi
8> 1
Alm No 1 Lo
9> 0
Alm No 1 Anlg
A> 1
Alm No 1 Pls
B> 1
Alm No 1 Quit
Q>
2
Information. Alarm 2 is identical to, but independent of,
Alarm 1.
3
Select high and low flow alarm trip points.
Alm Trip Hi
1>
Alm Trip Lo
2>
Alm Trip Hyst
3>
Alm Trip Disp
4>
Alm Trip Quit
Q>
Enter Q (CR) to return to Alm Menu or (CR) to cycle around this menu.
...APPENDIX B
Remarks
Select Alarm 1 output functions.
'1' = selected. '0' = deselected
Idle state for alarm output.
With no alarm active:
0 = Low (O/P transistor ON)
1 = High (O/P transistor OFF)
0 = Alarm output disabled (set to idle state).
1 = Alarm output enabled.
Alarm occurs for Measurement fault.
Alarm occurs for forward flow.
Alarm occurs for reverse flow.
Alarm occurs for Pulse Output Cutoff.
Alarm occurs for empty sensor.
Alarm occurs for Flow ≥ 'Alm Trip Hi'.
Alarm occurs for Flow ≤ 'Alm Trip Lo'.
Alarm occurs for Analogue Output Overange.
Alarm occurs for Pulse Output Overange.
Enter Q (CR) to return to Alm Menu or (CR) to
cycle around this menu.
Select Alarm 2 output functions.
High flow alarm trip point as % of range.
Low flow alarm trip point as % of range.
Enter hysteresis for alarms as % of range.
Set to '1' if Hi/Lo Alarms are to be displayed
(default = 0)
Enter Q (CR) to return to Alm Menu or (CR) to
cycle around this menu.
21