B.3: Mps-24A Main Power Supply; B.4: Mps-24B Main Power Supply - Honeywell NOTIFIER LDM Series Instruction Manual

Lamp driver module
Table of Contents

Advertisement

System 5000 (UL 8th)
B.3 MPS-24A Main Power Supply
Connect the power run for the LDMs to MPS-24A TB3, Terminals 1 (+) and 2 (-). Maximum current is 1 amp. The power run to the
LDMs need not contain a Power Supervision Relay since loss of power is inherently supervised.
B.4 MPS-24B Main Power Supply
Connect the power run for the LDMs to MPS-24B, TB2, Terminals 1 (+) and 2 (-). No more than 200 mA current can be drawn from
these terminals in standby or alarm.
CAUTION: POWER-LIMITED WIRING
!
THE +24 VDC PROVIDED ON TB2 TERMINAL 3 IS POWER-LIMITED ONLY WHEN USED WITH THE MINUS RETURN
ON TB2 TERMINAL 4. DO NOT USE THE MINUS RETURN ON TB2 TERMINAL 2 WITH THE +24 VDC POWER ON TB2
TERMINAL 3.
32
Common (-) TB3-2
24 VDC Power (+) TB3-1
TB1
EARTH GND
AC NEUTRAL
AC HOT
CB1
Figure B.2 Connecting Power from the MPS-24A
MPS-24B
(-) Common TB2-2
Figure B.3 Connecting Power from the MPS-24B
PO WER LIMITED
BA T +
BA T -
+24R COMMON
+24
COMMON
TB2
F1
P3
MPS-24A
24 VDC Power (+) TB2-1
LDM Series Instruction Manual — P/N 15885:H3 8/12/2019
MPS-24A Main Power Supply
P2
P5
P4
R27