Lamp/Led Wiring - Honeywell NOTIFIER LDM Series Instruction Manual

Lamp driver module
Table of Contents

Advertisement

Lamp/LED Wiring

below. If this module is used to drive both power-limited and nonpower-limited circuits, connect relays 1 to 16 to power-limited circuits
and connect relays 17 to 32 to nonpower-limited circuits or vice versa. Use an appropriate power-limited power supply which is UL
listed for fire alarm systems to provide power for the power-limited circuits.
4.9 Lamp/LED Wiring
NOTE: All LEDs/lamps being driven by the LDM series must be located in the same room as the modules. Use cable kits for wiring from
connectors on LDM.
Figure 4.8 illustrates LEDs being powered by the 5V output from LDM-32, J11 pin 1.
Figure 4.9 illustrates LEDs being powered by the 24V output from LDM-32, J9 pin 3.
LDM Series Instruction Manual — P/N 15885:H3 8/12/2019
Power-
Limited
Circuits
Figure 4.7 Wiring Requirements
Note: All LEDs must be in the same room as the LDM modules.
Point Status LEDs:
Use red for alarm points,
yellow for trouble points, and
green for output points
Use 680 W, 1/4 watt resistors for
each point if using 2 mA LEDs.
OUTPUTS
J6
J5
J11
+5
Common
J4
SW ITCH
MA TRIX
Figure 4.8 Typical LDM-to-Graphics Display Connection @ 5VDC
LDM-R32
J7
J8
J10
LAMP
J9
PO W ER
Wiring Considerations
Nonpower-
Limited
Circuits
Wiring is
not
supervised
System
Trouble LED
(Yellow)
Custom
Graphic
Display