3.3 Wire Routing

Follow power-limited wiring techniques. Maintain 0.25" spacing between power-limited and non-power-limited circuits and separate high
and low voltage circuits.
Route all low voltage
wiring through any of
these knockouts.
All circuits, except battery cables
and AC, are power limited.
Maintain at least 0.25" spacing
between power limited and non-
power limited circuits.
Separate high and low voltage
circuits.

3.4 AC Power

At installation, connect the AC terminals to a 120/240 VAC source as shown in Figure 3.3. It may be necessary for a professional electrician
to make this connection.
The AC terminals are rated 120 VAC, 50 or 60 Hz, 2.7 A (for the RPS-1000/B) or 240 VAC, 50 or 60 Hz, 1.4A (for the RPS-1000HV).
28
AC Power
N
G
L
3
2
1
RPS-1000 Board
battery cables
from under board
33
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
-
+
A
B
N.O.
C
N.C.
N.O.
C
N.C.
-
+
A
B
-
+
A
B
O
MAIN SBUS IN OUT
/
RELAY 1
RELAY 2
SBUS IN
SBUS OUT
I/O 1
red
black
Figure 3.2 Wire Routing Example
120VAC/240VAC input
hot
earth ground
neutral
N
L
3
2
1
Figure 3.3 AC Power Connection
Note: Board assembly shown without
Formex cover for illustration purposes
only. Formex cover must be used in all
installations.
Fire alarm power-limited circuits are
installed using types FPL, FPLR,
FPLP or permitted substitute cables,
14
13
12
11
10
9
8
7
6
5
4
provided these power-limited cable
X
O
X
O
X
O
X
O
X
O
X
I/O 2
I/O 3
I/O 4
I/O 5
I/O 6
conductors extending beyond the
jacket are separated by a minimum
of 0.25 in. (6.35 mm) or by a non-
conductive sleeve or non-conductive
barrier from all other conductors.
High voltage models will be labeled.
RPS-1000 Manual — P/N 151153:R 2/15/2022