G.1 Capabilities
When installed with an SFP-1024 Fire Alarm Control Panel (FACP), the LDM annunciator is used to provide an interface to a custom
graphic annunciator. All releases of SFP-1024 software can support LDM modules, no special software is required. The LDM can be
assigned to any of the panel annunciation points.
An LED-10IM Interface Module is required on the SFP-1024 to allow connection of annunciators to the panel. A maximum of 32
devices can be connected to the EIA-485 output of the LED-10IM Module.
For more information on annunciator operation and FACP programming under various specific applications, refer to the SFP-1024 doc-
uments referenced in Section 1.3, "Related Documentation", on page 7.
66
Appendix G: SFP-1024 (UL 8th)
(+) 24 VDC
(-) Nonresettable Power
24V NON
24V
RESETT ABLE
RELA Y 1
RELA Y 2
BELL 1
BELL 2
RESETT ABLE
TB2
TB3
TB4
SFP-1024
EIA-485 (-)
EIA-485 (+)
LED-10IM
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE 5
ZONE 6
ZONE 7
ZONE 8
ZONE 9
TB5
J10
CLASS A CONVERTER MOD
LDM Series Instruction Manual — P/N 15885:H3 8/12/2019
+ -
+ -
TB1
J1
ZONE 10
J6
LED-10IM INTERF ACE
MODULE