B.5: Configuration For The Ldm-32 And System 5000 - Honeywell NOTIFIER LDM Series Instruction Manual

Lamp driver module
Table of Contents

Advertisement

Configuration for the LDM-32 and System 5000
B.5 Configuration for the LDM-32 and System 5000
LDM-32 DIP Switch (SW3) settings (for System 5000):
1.
Relay Control: Future Use - this switch must be set OFF on the System 5000.
2.
Number of LDM-E32 Expanders Installed:
3.
Number of LDM-E32 Expanders Installed:
4.
8-Point Shift: Set switch ON to shift CPU-5000 LED function annunciation from the first eight annunciator positions on the
LDM-32 to the third LDM-E32 expander positions 57 - 64. This shift can only be set on an LDM-32 set for address 1.
5.
Receive Only: Set this switch ON for each LDM series that will provide the same information as another LDM series in a different
physical location (when two or more sets of LDM series have the same address, all but one must be configured as Receive Only.)
6.
Piezo Disable: Set this switch ON to disable the piezo from sounding for any event.
7.
Switch Inhibit: To disable the point I/O control switches on the LDMs from functioning, set this switch ON. When inhibited, the
local Lamp Test switch continues to function. In addition, the Acknowledge/Lamp Test switch will function only in a local capacity,
unrecognized by the host System 5000.
8.
Flash Inhibit: Set this switch ON to disable the flashing of LEDs associated with unacknowledged events. Flash Inhibit also
disables the piezo from sounding. Flash Inhibit must be ON when using the relay expander module (LDM-R32).
*The lamp driver can be set for addresses 1, 2, 3 or 4. The actual mapping arrangement for a respective module and its expanders
depends on System 5000 annunciator programming. Refer to Document 15584 for details.
LDM Series Instruction Manual — P/N 15885:H3 8/12/2019
Lamp Driver Address
Set in the range 01-04
DIP Switch SW3
(see settings below)
Switch set to
Switch set to
OFF position
ON position
Lamp Driver Mode Switch
Ones
Tens
ALARM/TROUBLE mode
(SW4 set to right side)
LDM-32
ALARM ONLY mode
(SW4 set to left side)
None
One
Two
OFF
ON
OFF
OFF
OFF
ON
System 5000 (UL 8th)
SW4
SW4
Four
ON
ON
33

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier ldm-32Notifier ldm-e32

Table of Contents