Honeywell NOTIFIER LDM Series Instruction Manual page 63

Lamp driver module
Table of Contents

Advertisement

Configuration for the LDM-32 and AFP-200
Figure E.4 illustrates configuration for the LDM to annunciate active and trouble states for the first 56 software zones with the last eight
points (16 LEDs) dedicated to the AFP-200 functions listed below.
It is assumed that the '8-Point Shift' will be selected only on systems containing less than 56 circuits.
LDM Series Instruction Manual — P/N 15885:H3 8/12/2019
Address #1
LDM-32
1 - 4
1st LDM-E32
17 - 20
2nd LDM-E32
33 - 36
3rd LDM-E32
49 - 52
Alarm
J5
not used
not used
Signals Silenced (Yellow LED)
System Trouble (Yellow LED)
System Alarm (Red LED)
OUTPUTS
Figure E.4 Activation/Trouble Operation With 8-Point Shift
9 - 12
5 - 8
25 - 28
21 - 24
41 - 44
37 - 40
53 - 56
System Status Indicators*
T rouble
Alarm
T rouble
Alarm
T rouble
J6
OUTPUTS
J7
View of LDM-32
* System Status Indicators
not used
not used
not used
not used
Supervisory (Yellow LED)
Pre-Alarm
AC Fail (Yellow LED)
not
Panel Trouble
J7
J8
AFP-200 (UL 8th)
13 - 16
29 - 32
45 - 48
Alarm
T rouble
J8
63