Wiring Specifications

Wiring Distance Calculation Example

Suppose a system is configured with the following SBUS modules:
2 - 5860 Fire Annunciators
1 - 5895XL Intelligent Power Expander
1 - 5865 LED Fire Annunciator
1 - 5824 Parallel/Serial Interface
The total worst case current is calculated as follows:
Using this value, and referring to the Wiring Distance table, it can be found that the available options are:
370 feet maximum using 22 Gauge wire
938 feet maximum using 18 Gauge wire
1493 feet maximum using 16 Gauge wire
2362 feet maximum using 14 Gauge wire
5895XL Manual — P/N 151142-L8:M 2/15/2022
5860 Current Draw
5895XL Current Draw
5865 Current Draw
5824 Current Draw
Total Worst Case Current Draw
= 2 x 0.100 amps
= 0.200 amps
= 1 x 0.010 amps
= 0.010 amps
= 1 x 0.200 amps
= 0.200 amps
= 1 x 0.040 amps
= 0.040 amps
= 0.450 amps