Commissioning
7 Commissioning
netTAP NT 151-CCIES-RE | CC-Link IE Field Slave to PROFINET IO-Device gateway
DOC180403UM01EN | Revision 1 | English | 2018-08 | Released | Public
Firmware
The netTAP NT 151 CCIES-RE is delivered with pre-loaded firmware and
can thus be instantly installed, configured and commissioned.
Configuration
The netTAP is to be configured with the Windows configuration software
SYCON.net via the USB interface of the device (see position
Positions of the interfaces and LEDs [} page 22]).
SYCON.net allows you to create a configuration "offline", without an actual
connection to the target device (i. e. the netTAP). Only for the subsequent
download of the configuration into the device, you need a physical USB
connection.
The device stores this data remanently, i.e. the data is being kept after
power off or device reset.
The device description files for configuring the CC-Link IE Field Master and
the PROFINET IO Controller can also be generated by SYCON.net.
Detailed information about configuration with SYCON.net can be
found in the operating instruction manual Configuration of Gateway
and Proxy Devices, DOC081201OIxxEN on the Gateway Solutions
DVD in the Documentation\english\1.Software
\SYCON.net Configuration Software\Configuration of
Gateway and Proxy Devices OI xx EN.pdf directory.
SD memory card option
In case an SD memory card containing a valid configuration is inserted into
the netTAP NT 151-CCIES-RE while a power-on cycle is being performed,
all data stored on the card will be copied to the internal load memory of the
device. (For the position of the memory card slot, see
Positions of the interfaces and LEDs [} page 22].)
Any old data stored in the load memory will be erased by this.
With this procedure, you can reset the device to its factory settings or load
a desired configuration without having to establish a USB connection to the
SYCON.net configuration software. SYCON.net offers the function to copy
the data of the internal load memory of an already configured netTAP onto
an inserted empty SD memory card. Thus, you can easily "clone" a
configuration and transfer it into another device, e.g. into a spare device in
case of a defective primary device.
Note that the SD card must be FAT formatted, otherwise it will not be
recognized by the device. Detailed instructions on how to transfer
configuration data into another netTAP device by SD memory card can be
found in chapter Using SD memory card to copy configuration data into
spare netTAP devices [} page 43].
Resetting the netTAP to its factory settings by using an SD memory card
(e.g. in case of a defective firmware) is described in the subsequent
chapter.
32/63
(8)
in section
(7)
in section
© Hilscher 2018