INERTIA-2464 Technical & Programming Manual

BATTERY TEST

This function tests the performance of the batteries fitted to the system. Pressing this button will initiate a
battery test as specified.
The test will temporarily disconnect the batteries from the panel and apply load on the batteries for 60
seconds. If the batteries are OK, the test will be performed for 60 seconds and then the panel will return to
normal. If the batteries fail the test, the "Battery Fault" LED will illuminate and the buzzer will sound.
The pressing of any key during the test period will abort the battery test and return the system back to normal
mode.
• NOTE: The batteries are also monitored for open or short circuit. If the batteries are open or short-
circuited for a period of 30 seconds the "Battery Fault" LED will illuminate and provide a common
fault. This automatic battery monitoring functions in quiescent mode and is therefore disabled if
there is an alarm present to avoid confusion.

AUTO TEST MODE

This function will perform a fixed automatic test procedure to the panel. This mode cannot be selected if any
zone(s) is in alarm.
Auto test will perform the following test functions;
Turn on ALL LEDs for 0.5 seconds
Test LCD Backlight
2
Test E
ROM
Test RAM
Test LCD
Isolate all alarm zones
Fault test all alarm zones
Alarm test all alarm zones
Test buzzer
TEXT The pressing of any key during "AUTO TEST" will abort the tests and return the system back to normal
mode once the current test is complete.
Note:
During "AUTO TEST", all zones are treated as zone type #1 (standard latching type with 2 second
delay). Once AUTO TEST has finished, all zones will be reset and returned back to their previously
configured types.
Copyright (c) 1996, INERTIA FIRE SYSTEMS
Page 17