Mounting, demounting and electric installationI

10.2 Installation notes

NOTICE
Comply with the required safety measures against electrostatic discharge (ESD)
acc. to EN 61340-5-1 when operating the extension modules.
Shielding connection for the extension module
To ensure EMC safety, connect all shieldings directly at the control cabinet
entrance to a common FE ground line.
The shielding connection set for the S20 modules may not be set for
the extension modules.
Mounting location
The extension modules have the degree of protection IP 20 and are thus
intended for use in a closed control cabinet or control box (terminal box) of
the degree of protection IP 54 or higher.
Mounting rail
Mount the extension modules on a 35 mm standard mounting rail. The
preferred overall height of the mounting rail is 7.5 mm (corresponds to TH
35-7.5 acc. to EN 60715).
Mount the extension modules and the extension bus base modules as
described in this chapter.
Install the extension modules on a horizontally mounted mounting rail.
The fastening distance of the mounting rails may not exceed 200 mm. This
distance is required to ensure stability while mounting and demounting the
control or the extension modules.
Fig. 10-2: Mounting rail fastening (in mm)
NOTICE
If screws and rivets are too high on the mounting rail, the bus base modules
do not really engage on the mounting rail. Use only screws and rivets with a
structural height of up to 3 mm to fasten the mounting rail.
End clamp
Bosch Rexroth AG R911345570_Edition 05
IndraControl XFE 01.1 Extension Mod-
ules Profibus, RT-Ethernet, Sercos, CAN
Danger
of
module
electrostatic discharge!
Electronic damage due to fastening elements
of the mounting rail
destruction
due
_
< 200
to