4. Storage

Before using the circuit breaker stored six (6) years or longer, oil the oiling points described in Inspection and
Maintenance. For details, please contact our service network.
+60℃
ok
-20℃
Average temperature for 24 hours,
however, shall not be higher than 35°C.
Do not store the uncovered circuit breaker.

5. Required tool

M12
Hexagon spanner
• To open and install the
circuit breaker.
• To connect the main
circuit.
E-8
Control humidity to prevent condensation.
Relative humidity: 85% max.
When storing the circuit breaker, cover it.
3 mm
Flat tipped screwdriver
• To set the electronic trip
relay.
No direct sunlight.
H
H
S (Hydrogen sulfide) 0.01 ppm max.
2
SO
(Sulfur Dioxide) 0.05 ppm max.
2
NH
(Ammonia) 0.25 ppm max.
3
Before storing the circuit breaker, turn it OFF.
PH2
Phillips screwdriver
• For the control circuit
terminal block.
NH
3
S
SO
2
2
OFF
M8
Hexagon wrench
• To remove and install the
universal terminal.