MITSUBISHI Low-Voltage Air Circuit Breakers type AE
CC-Link Interface unit (BIF-CC)
INSTRUCTION MANUAL
ACB types covered in this manual
AE630-SW
AE2000-SWA
AE2000-SW AE2500-SW AE3200-SW
AE4000-SWA
AE4000-SW AE5000-SW AE6300-SW
IMPORTANT NOTE:
instructions carefully, and make sure that all actual users also read them.
AE1000-SW AE1250-SW AE1600-SW
Before using these Series AE breakers, please read these

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric AE630-SW

  • Page 1 MITSUBISHI Low-Voltage Air Circuit Breakers type AE CC-Link Interface unit (BIF-CC) INSTRUCTION MANUAL ACB types covered in this manual AE630-SW AE1000-SW AE1250-SW AE1600-SW AE2000-SWA AE2000-SW AE2500-SW AE3200-SW AE4000-SWA AE4000-SW AE5000-SW AE6300-SW IMPORTANT NOTE: Before using these Series AE breakers, please read these...
  • Page 2 ● SAFETY PRECAUTIONS ● Make sure to observe the following matters of safety  Before using the device, make sure to read these safety precautions and instruction manual thoroughly. The cautionary items noted herein are of the utmost importance for the safe use of this device, and should always be strictly followed. ...
  • Page 3 ■EMC Directive In IEC60947-2, following EMC tests are required. 1) Radiated radio frequency emission 2) Radiated radio frequency electromagnetic field immunity BIF-CC is confirmed to IEC60947-2 in accordance with following conditions. 1) BIF-CC shall be installed in the panel board. It effects not only for safe against electric shock but also to interrupt noise emission from the device.
  • Page 4: Table Of Contents

    - Table of Contents - 1. System Overview ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 2. Specifications 2.1 BIF-CC ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 2.2 BIF-CON (Option) ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 3. Part Names and Settings 3.1 BIF-CC ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 3.2 BIF-CON (Option) ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 4. Installation 4.1 IEC rail installation ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 4.2 Bracket installation ・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・ 5.
  • Page 5: System Overview

    1. System Overview BIF-CC (CC-Link Interface unit) is used for monitoring and operating ACB with CC-Link network. ●Monitoring: - Measurement items (current, voltage, power, harmonics, energy, etc) - Trip and alarm information (present status, history) - Breaker status (Breaker ON/OFF status, Position of Breaker (*BIF-CON and BIF-CL is required)). ●Operating: - Breaker control (ON/OFF/Spring charge) (*CC/SHT/MD and BIF-CON is required).
  • Page 6: Specifications

    2. Specifications 2.1 BIF-CC The general specifications of BIF-CC are shown in table 2.1. Table 2.1 General specification of BIF-CC Item Specifications Type name BIF-CC Power supply 100-240V AC・DC (50/60Hz) 3VA (not including BIF-CON) Power consumption 5VA (including BIF-CON) External dimensions 100(H) x 90(W) x 65(D) Operating ambient temperature -5 to +40℃...
  • Page 7: Bif-Con (Option)

    2.2 BIF-CON (Option) The general specifications of BIF-CON are shown in table 2.3. Table 2.3 General specifications of BIF-CON Item Specifications Type name BIF-CON Power supply Supplied from BIF-CC Number of channel 3 channels (INPUT1, INPUT2, INPUT3 general use) Digital input Isolation Photo coupler isolation Signal level...
  • Page 8: Part Names And Settings

    3. Part Names and Settings 3.1 BIF-CC The unit overview is shown as below. Fig 3.1: Front view Fig 3.2: Side view ●(A) LED Name Indication Description Power is supplied correctly POWER Power is not supplied Flashing Internal transmission error has occurred T ERR.
  • Page 9 ●(B) RESET Switch RESET Switch is used to reset the BIF-CC without power supply off. After changing the STATION NO. switch or B RATE switch while power supply is on, push this switch. ●(C) Terminals Screw Name Description Notes (Tighten torque) 1.
  • Page 10 ●(D) STATION NO. Switch The BIF-CC supports the station number range from 1 through 64. The station number is set in binary form shown as below sample. The setting of switches is effective when power supply is turned ON. “(B) RESET switch” After changing the switch while power supply is on, push RESET switch (see also STATION NO.
  • Page 11 ●(G) Connector for I/O unit (BIF-CON) connection This connector is used for connection to I/O unit (BIF-CON). Wiring connection is shown as below. BIF-CON cable (200mm) (*attached to BIF-CON) Keep distance more than 100mm from the power distribution circuit. Hot plugging is not permitted Fig 3.7: Wiring Connection ●(H) IEC rail latch...
  • Page 12: Bif-Con (Option)

    3.2 BIF-CON (Option) The unit overview is shown as below. Fig 3.7: Front view Fig 3.8: Side view ●(A) LEDs Name Indication Description Power is supplied from BIF-CC correctly POWER Power is not supplied 1a contact for SHT is closed (500ms) 1a contact for SHT is open 1a contact for CC...
  • Page 13 ●(B) Terminals Screw Name Description (Tighten torque) C1, C2 Output terminals for SHT A1, A2 Output terminals for CC U1, U2 Output terminals for MD Digital input1 terminal (0.5 to 0.6N.m) max. 6mm Digital input2 terminal Digital input3 terminal Input common Fig 3.10: Crimp-type terminal ”7.
  • Page 14 ●(C) REMOTE/LOCAL switch The REMOTE/LOCAL switch is used for change over of remote/local control of AE-SW. When this switch is in REMOTE position, the remote control (ACB ON/OFF and charging the spring) are available via CC-Link network. When this switch is in LOCAL position, the remote control cannot be operated. ●(D) Connector for AE-SW Drawout position switch (BIF-CL) connection This connector is used for connection to BIF-CL (*Option).
  • Page 15 ●(E) Connector for BIF-CC connection This connector is used for connection to BIF-CC. Wiring connection is shown as below. BIF-CON cable (200mm) (*attached to BIF-CON) Keep distance more than 100mm from the power distribution circuit. Hot plugging is not permitted BIF-CC BIF-CON Fig 3.13 Wiring Connection...
  • Page 16: Installation

    4. Installation 4.1 IEC rail installation The 35mm IEC rail (DIN rail) installing and removing procedure of BIF-CC and BIF-CON are shown as below. The applicable IEC rail is shown in figure 4.1. (A) Installing ①Hook on the upper side of rail Fig 4.1: 35mm IEC rail ②Push BIF-CC/BIF-CON into rail until it clicks Fig 4.2: Installing...
  • Page 17: Bracket Installation

    4.2 Bracket installation The mounting bracket installation of BIF-CC and BIF-CON are shown as below. Mounting bracket Mounting φ4.5 hole Fig 4.5: Mounting bracket Installation of BIF-CC/BIF-CON E-17...
  • Page 18: Communication Items

    5. Communication items 5.1 Communication items In the table 5.1 shown below, the available communication items using BIF-CC are presented. Especially, the details of a “5.2 Measurement items (detail)” ” 5.3 Setting items (detail)” measuring and setting items are described in respectively.
  • Page 19 Table 5.1: Communication items (2/3) Required Communication items Descriptions option ■Items for ETR Trip cause Transmitted the cause using bit data when trip has occurred. INST E1 and ZCT Trip history fault cause The trip information (last 10 trips) are stored in the EEPROM. However, when Power supply module (P1-P5) is off, current any trip information are not stored.
  • Page 20 Table 5.1: Communication items (3/3) Required Communication items Descriptions option ■Items for setting (*For details, see “5.3 Setting items (detail)” Date and time year/month/day/hour/minute/second Monitoring and setting of date and time are available. Demand time load current Set the demand time used for demand measuring values. leakage current E1 and ZCT power (active/reactive/apparent)
  • Page 21: Measurement Items (Detail)

    5.2 Measurement items (detail) The detailed specifications for measurement items are shown in table 5.2. Detailed specifications for measurement items Table 5.2: Phase-Wire Items (Accuracy) Unit Measurement range Cut off 3φ3W 3φ4W [0.1A] (*In< 500A) 5) Load current (±2.5% 0 to 2×In [A] △...
  • Page 22: Troubleshooting

    6. Troubleshooting In this chapter, the causes and corrective actions for errors that may occur when using BIF-CC are described. Please take action appropriately according to the following when the error occurs. If the error is not canceled by the following actions, please contact your nearest MITSUBISHI representative. 6.1 Errors detected by BIF-CC The errors detected by BIF-CC (LED indication) are shown in table 6.1.
  • Page 23 E-23...
  • Page 24: Outline Dimensions

    7. Outline dimensions ●BIF-CC ●BIF-CON E-24...
  • Page 25: Service Network

    8. SERVICE NETWORK E-25...