8.3 Check of the N-pole (4-Pole)

The position of N-pole is selectable. Check the label on the rear side of the circuit breaker before connecting.
■ Fixed type

8.4 Control circuit

■ Crimp-type terminal size
Use the connection terminals for M3.5. For
the size, refer to the right figure.
The recommended terminal is shown below.
Ex. 1.25 mm
N2-M3 (RAP2-3.5)
FN2-M3 (RBP2-3.5)
N2-YS3A
Manufacturer: J.S.T. Mfg. Co.,Ltd.
(Note)
If the screw is tightened with excessive
torque, the crimp-type terminal and the
screw may be damaged. Tighten the
screw with the specified torque.
Use a screwdriver that is suitable for the
size of cruciform groove.
Size of toolhead : PH2
E-22
N-pole: Left (Option)
N-pole: Left (Option)
N-pole: Right (Standard)
N-pole: Right (Standard)
2
2
to 2.0 mm
wires
■ Drawout type
M3.5 × 10
Torque: 1.0±0.2 N・m
Passage wiring
CAUTION
Cap
Cap
N-pole: Left (Option)
N-pole: Left (Option)
N-pole: Right (Standard)
N-pole: Right (Standard)
7.2 mm max.
  
Since voltage is applied to the terminals
S1 and S2 , do not touch them.
When an UVT is installed, voltage is
applied to DT1 and DT2 of the terminal
block. Do not touch the terminals.When
not using S1 , S2 , DT1 , and DT2 , do
not remove the caps on them for safety.