15. Cell switch (CL)

15.1 How to check the specifi cations
The terminal screws on the cell switch are arranged corresponding to the terminal numbers on the rated nameplate.
* In case of CL: 2C1T1D

15.2 How to connect terminals

Connect the wire to the terminal block within
the specified tightening torque. The following
table lists the drawout position depending on
the specifications of the cell switch.
Wire the lead wires through the lead wire hole
on the top of the circuit breaker and fix them in
the terminal block with screws.
When wiring, do not damage the lead wires. Wire
them so that the excessive tension is not applied
to them when the circuit breaker operates.
After wiring, check that the wires do not interfere
with the operation of the circuit breaker and
the output properly switches depending on the
drawout position.
Specifications
CL-C
CL-T
CL-D
(Note)
Overtightening can cause damage to
the terminals and/or screws.
The terminal screws are M4 binding head
screws. The following figure shows an available
solderless terminal.
E-30
Nameplate 1
Terminal screw
Nameplate 2
Position for the drawout operation
CONNECT
TEST
DISCONNECT
4.3
20 mm or shorter
Option
Terminal number
Terminal screw (M4)
Tightening torque: 0.98±0.2 N・m
Drawout type
Cell switch
Lead wire hole
Terminal block