1. CONTROLS
1-4. System Control Interface [MAC-333IF-E], cont.
10. Setting Signal Output
Connecting the SYSTEM CONTROL Interface
Each relay can be turned ON/OFF by synchronizing with the room air conditioner's ON/OFF, error/normal, Heater
ON/Heater OFF, and Humidifier ON/Humidifier OFF.
Interface unit
Indoor unit
SW500
SW502
2
Please use the cable of 0.5mm
[AWG20] or more.
The cable must fit into TB530 and meet DC12V power supply.
Notes
• Connecting terminal TB530 for power supply is polarized, so confirm proper polarity of the terminals before connecting.
• Do not connect DC12V from the DC power supply to TB571.
• Confirm polarity when using a diode built-in relay. C of TB571 is electropositive potential
● For TB571 and TB530, insert wiring after inserting the flathead screwdriver into the terminal.
● Appropriate electric wire for TB571 and TB530 is as follows. Stranded wire: 0.3mm
[ø1/64in. to ø3/64in.]
● Peeling dimension of the electric wire for TB571 and TB530 is 7mm to 10mm [9/32in. to 25/64in.].
● Wiring length from the interface to Relay 1 and Relay 2 should be less than 50m [164ft].
Setting when using Status Signal Output
F
u
n
t c
o i
n
s
ON
1
ON/OFF, Error/
Normal Output
ON
1
ON
1
ON/OFF, Heater
Control Output
ON
1
ON
ON/OFF,
1
Humidifier Control
Output
ON
1
ON
Heater Control,
1
Humidifier Control
Output
ON
1
Due to continuing improvement, above specification may be subject to change without notice.
58
+
R2
R1
C
TB571
TB530
(Gray) (Sky
Blue)
DC 12V
CN560
power
supply
+
DC power supply: DC 12V (+10%, -0%) 5W or more. Please use
power supply with double insulation or reinforced insulation.
S
W
N
. o
SW500
SW502-1: OFF
• Relay 1 is on when room air conditioner is on, and off when room air conditioner is off.
2
3
4
5
6
7
8
SW502
• Relay 2 is on when room air conditioner is in error, and off when room air conditioner is operating normally.
ON
SW502-1: ON
• Relay 1 and 2 behavior are opposite of those above.
2
3
4
5
6
7
8
OFF
SW500
SW502-1: OFF
• Relay 1 is on when room air conditioner is on, and off when room air conditioner is off.
• When the air conditioner runs in the heating (automatic heating) mode and room temperature becomes the
2
3
4
5
6
7
8
set temperature - 4.5 ºF (2.5 ºC) or lower, the Relay 2 (heater) turns on.
SW502
When the air conditioner runs in a mode other than the heating (automatic heating) or it is OFF, or when room
ON
temperature becomes the set temperature or higher, the Relay 2 (heater) turns off.
SW502-1: ON
2
3
4
5
6
7
8
• Relay 1 and 2 behavior are opposite of those above.
OFF
SW500
SW502-1: OFF
• Relay 1 is on when room air conditioner is on, and off when room air conditioner is off.
2
3
4
5
6
7
8
• When the air conditioner runs in the heating (automatic heating) mode, Relay 2 (humidifier) turns on. When the
SW502
air conditioner runs in a mode other than heating (automatic heating) or it is OFF, Relay 2 (humidifier) turns off.
ON
SW502-1: ON
• Relay 1 and 2 behavior are opposite of those above.
2
3
4
5
6
7
8
OFF
SW502-1: OFF
SW500
• When the air conditioner runs in the heating (automatic heating) mode and room temperature be-
comes the set temperature - 4.5 ºF (2.5 ºC) or lower, Relay 1 (heater) turns on.
When the air conditioner runs in a mode other than the heating (automatic heating) or it is OFF, or
2
3
4
5
6
7
8
SW502
when room temperature becomes the set temperature or higher, Relay 1 (heater) turns off.
ON
• When the air conditioner runs in the heating (automatic heating) mode, Relay 2 (humidifier) turns on. When the
air conditioner runs in a mode other than heating (automatic heating) or OFF, Relay 2 (humidifier) turns off.
SW502-1: ON
2
3
4
5
6
7
8
OFF
• Relay 1 and 2 behavior are opposite of those above.
M-Series - Controls (December 2016)
R2
Relay 2
Relay 1, 2:
(Coil rating of DC 12V, 1.0W or
R1
less.) Please use relays with
reinforced insulation.
Relay 1
+
, and R1 and R2 are negative potential
2
to 1.25mm
2
[AWG22 to 16] Solid wire: ø0.4mm to ø1.2mm
O
p
r e
t a
n i
g
d
e
a t
s l i
Driver
Terminal
Do not insert more than one
connecting cable into each
terminal of TB571 and TB530.
.