1. CONTROLS
1-2. Wired Remote Controller [PAR-32MAA-J], cont.
Table 3
Function
External static pressure
Table 4
MVZ, PVA
Function
Heater OFF
Inlet air temp.
Heater ON
Inlet air temp.
•The fan will stop and the heater will turn off when [DEFROST] or [ERROR] is displayed.
Enable heater
1st
basic control
Heater OFF
Inlet air temp.
Heater ON
Inlet air temp.
•The fan will stop and the heater will turn off when [DEFROST] is displayed.
1st
Inlet air temp.
Heater output
Heater
Enable heater
control
comfort mode
Heater OFF
Inlet air temp.
Heater ON
Inlet air temp.
•The fan will stop and the heater will turn off when [DEFROST] is displayed.
2nd
Heater OFF
Inlet air temp.
Heater ON
Inlet air temp.
•The fan will stop and the heater will turn off when [DEFROST] is displayed.
Enable heater
1st
economy mode
1st: Heater output from CN24-1 (yellow) on the indoor unit control board.
2nd: Heater output from CN24-2 (Blue) on the indoor unit control board.
Due to continuing improvement, above specification may be subject to change without notice.
© 2016 Mitsubishi Electric US, Inc.
Setting No. of
Mode No. 08 Mode No. 10
1
2
1
3
1
2
2
3
Setting
set temp
set temp - 4.5°F(2.5°C)
Inlet air temp.
Heater output
set temp
set temp - 1.8°F(1°C)
set temp
set temp - 2.7°F(1.5°C)
Inlet air temp.
Heater output
set temp - 1.8°F(1°C)
set temp - 3.6°F(2°C)
Inlet air temp.
Heater output
SEZ, PEA
PEAD
15 Pa
-
35 Pa
35 Pa
50 Pa
50 Pa
5 Pa
70 Pa
-
100 Pa
-
150 Pa
Set temp.
(Room temperature setting)
Set temp. -1.8°F (1°C)
Set temp. -4.5°F (2.5°C)
ON
OFF
Set temp.
(Room temperature setting)
Set temp. -1.8°F (1°C)
ON
OFF
Set temp.
(Room temperature setting)
Set temp. -1.8°F (1°C)
Set temp. -2.7°F (1.5°C)
ON
OFF
Set temp.
(Room temperature setting)
Set temp. -1.8°F (1°C)
Set temp. -4.5°F (2.5°C)
ON
OFF
M-Series - Controls (December 2016)
MVZ, PVA
75 Pa
Vertical, Horizontal Left, Horizontal Right
125 Pa
External Static Pressure Setting
200 Pa
75 Pa
125 Pa
Down flow External Static Pressure Setting
200 Pa
Mode No.
( )RF thermostat
setup function No.
23
11
(123)
(111)
1
-
2
2
Initial setting
(Factory setting)
1
2
21