1. CONTROLS
1-2. Wired Remote Controller [PAR-32MAA-J], cont.
[3] Use the F1 or F2 button to move
the cursor to select the mode
number, and change the setting
number with the F3 or F4 button.
Note:
• Make the above settings on Mr. Slim units as necessary.
• Refer to the Instructions Book when it is necessary to set the settings for City Multi units.
• Table 1 summarizes the setting options for each mode number. Refer to the indoor unit Installation Manual for the
detailed information about initial settings, mode numbers, and setting numbers for the indoor units.
• Be sure to write down the settings for all functions if any of the initial settings has been changed after the completion of
installation work.
Table 1. Function setting options
Table1. Function setting options
Mode No.
Mode
01
Automatic recovery after power failure
Function
02
Thermistor selection
(indoor temperature detection)
Disable
03
LOSSNAY connection
Power failure
automatic recovery
Enable (Four minutes of standby time is
required after the restoration of power)
04
Power voltage
Average temperature reading of the indoor
units in operation
Thermistor
05
AUTO mode
selection
Thermistor on the indoor unit to which the
07
Filter sign
(Indoor temperature
remote controller is connected (fixed)
detection)
Built-in sensor on the remote controller
08
Fan speed
Not supported
09
Outlet
LOSSNAY
Supported (Indoor unit does not intake out-
connectivity
door air through LOSSNAY.)
Supported (Indoor unit intakes outdoor air
10
Optional parts
through LOSSNAY.)
(High-efficiency filter)
11
Vane
230V
Power voltage
208V
(4) LOSSNAY setting (City Multi only)
This setting is required only when the operation of City Multi units is interlocked with LOSSNAY units. This setting is not available for the
2°C [36 °F] (Normal)
Frost prevention
Mr. Slim units. Interlock settings can be made for the indoor unit to which the remote controller is connected. (They can also be
temperature
confirmed or deleted.)
3°C [37°F]
Heat operation & Thermo ON
Note:
• Use the centralized controller to make the settings if it is connected.
Humidifier control
• To interlock the operation of the indoor units with the LOSSNAY units, be sure to interlock the addresses of ALL indoor
Heat operation
units in the group and that of the LOSSNAY unit.
Standard
[Button operation]
Change of
defrosting control
[1] When "Lossnay" on the Service
For high humidity
menu is selected, the remote
controller will automatically begin
( )RF thermostat setup function No.
searching for the registered
LOSSNAY addresses of the
currently connected indoor unit.
To make LOSSNAY interlock setting
[3] Enter the addresses of the indoor unit and the LOSSNAY unit to be
interlocked, with the F1 through F4 buttons, select "Set" in the
"Function", and press the SELECT button to save the settings.
"Sending data" will appear on the screen. If the setting is
successfully completed, "Setting completed" will appear.
Due to continuing improvement, above specification may be subject to change without notice.
18
Function setting
Ref. address
Unt # 1
Mode 7
Mode 8
Mode 9
Mode11
Request:
Cursor
Cursor
Individual items
(Unit No. 1 through 4)
Disable
Enable (Four minutes of standby time is required after the restoration of power.)
Settings
Average temperature reading of the indoor units in operation
Thermistor on the indoor unit to which the remote controller is connected (fixed)
Built-in sensor on the remote controller
Not connected
Connected (without outdoor air intake by the indoor units )
Connected (with outdoor air intake by the indoor units )
240 V
220 V, 230 V
Enable (Automatically the unit achieves effective energy saving operation.)
Disable
100 hours
2500 hours
Not displayed
Silent mode (or standard)
Standard (or High ceiling 1)
High ceiling (or High ceiling 2)
4 directional
3 directional
2 directional
No
Yes
No vanes (or the vane setting No.3 is effective.)
Equipped with vanes (The vane setting No.1 is effective.)
Equipped with vanes (The vane setting No.2 is effective.)
Lossnay
IU address
Lossnay address
Collecting data
M-Series - Controls (December 2016)
[4] When the settings are completed,
press the SELECT button to send
the setting data from the remote
controller to the indoor units.
[5] When the transmission is
successfully completed, the screen
will return to the Function setting
screen.
Settings
Mode
Setting
No.
No.
P-Series
1
01
(101)
2
1
02
2
(-)
3
1
03
2
(103)
3
1
04
(104)
2
1
15
(115)
2
1
16
(116)
2
1
17
[2] When the search is completed,
(117)
2
the smallest address of the
indoor units that are connected
to the remote controller and the
address of the interlocked
LOSSNAY unit will appear. "--"
will appear if no LOSSNAY unit
is interlocked with the indoor
units.
If no settings need to be made, press the RETURN button to go
back to the Service menu.
Lossnay
IU address
Lossnay address
Sending data
Function setting
Ref. address
Sending data
Setting No.
Unit numbers
OUTDOOR UNIT
1
Set "Grp." for the Unit number.
2
These settings apply to all the connected
MXZ-
MXZ-8C
indoor units.
PUMY
1
2C/3C/4C/5C
(PAC-MKA*BC)
2
3
1
2
3
1
2
1
2
1
2
Set "1, 2, 3, 4, or All" for the Unit number.
These settings apply to each indoor unit.
3
• If "1, 2, 3, or 4" is set for the Unit number,
1
the settings apply only to the specified
indoor unit regardless of the number of
2
connected indoor units (one through four
3
units).
1
• If "ALL" is set for the Unit number, the
2
settings apply to all the connected indoor
units regardless of the number of
3
connected indoor units (one through four
1
units).
2
1
2
3
-
-
-
-
-
-
Lossnay
IU address
Lossnay address
Function Set/Conf/Del.
Select:
Cursor
Lossnay
IU address
Lossnay address
Setting completed
Return:
© 2016 Mitsubishi Electric US, Inc.
MXZ-8B