1. CONTROLS
1-3. Simple MA Remote Controller [PAC-YT53CRAU], cont.
- When LOSSNAY or OA processing unit are not registered
4 If registration is unnecessary, end registration by pressing and holding down the [
[TEMP.
] buttons at the same time for two seconds.
If a new LOSSNAY or OA processing unit must be registered, go to step 1. Registration
procedure.
If you want to confirm another LOSSNAY or OA processing unit, go to step 2. Confirmation
procedure. To delete a registered LOSSNAY or OA processing unit, go to step 3. Deletion
procedure.
<1. Registration procedure>
5 Set the address of the indoor unit to be interlocked with the LOSSNAY unit using the [TEMP.
and [TEMP.
] buttons. (01 to 50)
6 After setting, press the [
operating the [TEMP.
LOSSNAY or OA processing unit address
Indoor unit address
7 Press the [ON/OFF] button, and register the set indoor unit address and LOSSNAY address.
- Registration end display
The indoor unit address and "IC" and LOSSNAY address and "LC" are alternately displayed.
- Registration error display
If the address is not registered correctly, the indoor unit address and [
LOSSNAY (or OA processing unit address) and [
Cannot be registered because the registered indoor unit or LOSSNAY or OA processing unit does
not exist.
Cannot be registered because another LOSSNAY or OA processing unit was registered at the
registered indoor unit.
Due to continuing improvement, above specification may be subject to change without notice.
© 2016 Mitsubishi Electric US, Inc.
FAN] button and set the Lossnay address you want to register by
] and [TEMP.
] buttons. (01~50)
] are alternately displayed.
M-Series - Controls (December 2016)
FAN] and
]
], and the registered