Danfoss VLT AutomationDrive EZ FC 321 Installation Manual page 30

Hide thumbs Also See for VLT AutomationDrive EZ FC 321:
Table of Contents

Advertisement

VLT®AutomationDrive EZ FC 321
Installation Guide
Enclo-
Enclo-
Voltage [V]
sure
sure
(1)
size
B1
Type 4X
200–240 V
(T2)
B1
Type 4X
380–500 V
(T5)
B1
Type 4X
380–500 V
(T5)
B1
Type 4X
525–600 V
(T6)
B2
Type 4X
380–500 V
(T5)
B2
Type 4X
525–600 V
(T6)
C1
Type 4X
380–500 V
(T5)
C2
Type 4X
380–500 V
(T5)
Only Type 4X enclosures can be used. Not valid for Open type (IP20) units.
1
Danfoss A/S © 2021.05
Power [hp]
Maximum in-
HO
terrupting
rating for lis-
ted circuit
breakers
7.5, 10
Specific type
15, 20
Specific type
15, 20
100 kA
15, 20
50 kA
25, 30
100 kA
25, 30
35 kA
40, 50, 60
100 kA
75, 100
100 kA
Maxi-
Further information
mum
ampere
rating
[A]
40–54
ABB MS165-54 480V/277Y 65 kA.
40–54
ABB MS165-54 480V/277Y 65 kA.
60
Any UL 489 circuit breaker type with maximum
interrupt rating and maximum ampere rating
in list.
40
Any UL 489 circuit breaker type with maximum
interrupt rating and maximum ampere rating
in list.
100
Any UL 489 circuit breaker type with maximum
interrupt rating and maximum ampere rating
in list
60
any UL 489 circuit breaker type with maximum
interrupt rating and maximum ampere rating
in list.
200
Any UL 489 circuit breaker type with maximum
interrupt rating and maximum ampere rating
in list.
250
Any UL 489 circuit breaker type with maximum
interrupt rating and maximum ampere rating
in list.
AN354546796134en-000201 / 130R0954 | 29