VLT®AutomationDrive EZ FC 321
Installation Guide
Enclosure
Power [hp]
Recommended fuse
size
40
gG-80
C1
40
gG-80
50
gG-100
60
gG-160
C2
75
aR-200
100
aR-250
C3
50
gG-100
60
gG-160
C4
75
aR-200
100
aR-250
D1h/D3h
125
aR-315
150
aR-350
200
aR-400
Table 15: 525–600 V, Enclosure Sizes A, B, C, and D
Enclosure
Power [hp]
Recommended fuse
size
A2
1.0-5.0
gG-10
A3
7.5
gG-10
10
gG-16
A5
7.5
gG-10
10
gG-16
B1
15
gG-25
20
gG-32
25
gG-40
B2
30
gG-50
40
gG-63
B3
15
gG-25
20
gG-32
B4
25
gG-40
30
gG-50
40
gG-63
C1
50
gG-63
Danfoss A/S © 2021.05
Recommended max-
Recommended circuit breaker
imum fuse
Eaton/Moeller
gG-160
NZMB2-A200
aR-250
NZMB2-A250
gG-150
NZMB2-A200
gG-160
aR-250
NZMB2-A250
aR-315
aR-350
aR-400
Recommended max-
Recommended circuit breaker
imum fuse
Eaton/Moeller
gG-25
PKZM0-25
gG-32
PKZM0-25
gG-32
PKZM0-25
gG-80
PKZM4-63
gG-100
NZMB1-A100
gG-63
PKZM4-50
gG-125
NZMB1-A100
gG-160
NZMB2-A200
Electrical Installation
Maximum trip
level [A]
160
250
150
250
Maximum trip lev-
el [A]
25
25
25
63
100
50
100
160