Electrical Installation - Danfoss VLT AutomationDrive EZ FC 321 Installation Manual

Hide thumbs Also See for VLT AutomationDrive EZ FC 321:
Table of Contents

Advertisement

VLT®AutomationDrive EZ FC 321
Installation Guide

4 Electrical Installation

4.1 EMC-compliant Installation
To obtain an EMC-compliant installation, refer to the wiring schematic (see
structions.
Also, remember to practice the following:
When using relays, control cables, a signal interface, fieldbus, or brake, connect the shield to the enclosure at both ends. If the
ground path has high impedance, is noisy, or is carrying current, break the shield connection on 1 end to avoid ground current
loops.
Convey the currents back to the unit using a metal mounting plate. Ensure good electrical contact from the mounting plate
through the mounting screws to the drive chassis.
Use shielded cables for motor output cables. An alternative is unshielded motor cables within metal conduit.
Ensure that motor and brake cables are as short as possible to reduce the interference level from the entire system.
Provide a minimum 200 mm (7.9 in) separation between mains input, motor cables, and control cables.
For communication and command/control lines, follow the particular communication protocol standards. For example, USB
must use shielded cables, but RS485/ethernet can use shielded UTP or unshielded UTP cables.
Ensure that all control terminal connections are PELV.
TWISTED SHIELD ENDS (PIGTAILS)
Twisted shield ends increase the shield impedance at higher frequencies, which reduces the shield effect and increases the leak-
age current.
-
Use integrated shield clamps instead of twisted shield ends.
SHIELDED CABLES
If shielded cables or metal conduits are not used, the unit and the installation do not meet regulatory limits on radio frequency
(RF) emission levels.
EMC INTERFERENCE
Failure to isolate power, motor, and control cables can result in unintended behavior or reduced performance.
-
Use shielded cables for motor and control wiring.
-
Provide a minimum 200 mm (7.9 in) separation between mains input, motor cables, and control cables.
INSTALLATION AT HIGH ALTITUDE
There is a risk for overvoltage. Isolation between components and critical parts could be insufficient and may not comply with
PELV requirements.
-
Use external protective devices or galvanic isolation. For installations above 2000 m (6500 ft) altitude, contact Danfoss re-
garding protective extra low voltage (PELV) compliance.
PROTECTIVE EXTRA LOW VOLTAGE (PELV) COMPLIANCE
Prevent electric shock by using PELV electrical supply and complying with local and national PELV regulations.
12 | Danfoss A/S © 2021.05
Illustration
N O T I C E
N O T I C E
N O T I C E
N O T I C E
N O T I C E
Electrical Installation
5) and follow the electrical installation in-
AN354546796134en-000201 / 130R0954

Advertisement

Table of Contents
loading

Table of Contents