Heaters

Description of Operation
W
hen the room temperature falls to "room set point - heater offset - heater
differential" (point 13), the heaters turn on. When the room temperature
rises to "room set point - heater offset" (point 14), the heaters turn off.
Adjusting the Heater Parameters
TO ADJUST THE HEATER DIFFERENTIAL
The heater differential can be adjusted to 1°F(0.6°C) or 2°F(1.1°C):
Set switch # 5 to ON to adjust the
heater differential to 1°F (0.6°C).
Set switch # 5 to OFF to adjust the
heater differential to 2°F (1.1°C).
42
TC4-2N6F.rev.07
(
Refer to figure 6 below)