Mist

Description of Operation
W
hen the room temperature rises to "room set point + band width 1 +
0.5°F (0.3°C) + differential 2 + differential 3 + curtain dead band +
differential 5 + mist differential" (point 11), the mist begins to operate
according to the mist timer settings. When the room temperature falls to
"room set point + band width 1 + 0.5°F (0.3°C) + differential 2 +
differential 3 + curtain dead band + differential 5 + mist differential - 1°F
(0.6°C)" (point 12), the mist stops operating.
40
TC4-2N6F.rev.07
(
Refer to figure 5 below)
Mist timer:
During TIME ON, the mist is
on. During TIME OFF, the mist
is off.