TO ADJUST THE OUTSIDE SET POINT
Set the parameter selection knob to OUTSIDE SETTINGS. The
outside temperature appears on the display.
Press the push-button. The outside set point appears flashing
on the display.
Using the adjustment knob, adjust the outside set point to the
desired value.
Press the push-button once again. If the outside set point is
presently activated, the word ON appears flashing on the
display. If the outside set point is presently deactivated, the word
OFF appears flashing on the display.
Turn the adjustment knob clockwise to activate the outside set
point (the word ON then appears flashing on the display) or
counterclockwise to inactivate the outside set point (the word
OFF then appears flashing on the display).

Stage 1 Fans

Description of Operation
Minimum ventilation cycle
1
When the room temperature is below the room set point, the stage 1 fans
run according to the stage 1 timer settings.
(
Refer to figure 1 on next page)
Stage 1 timer:
During TIME ON, the fans run at
minimum speed. During TIME
OFF, the fans do not run.