A4... with HS5E(V)(L) control system Series 1x and 30 | Commissioning
Bosch Rexroth AG, RE 92076-01-B/2021-04-22
Fig. 31: Good control
If the control behavior is good, no further measures are required.

8.1.8 Calibrating the HS5E(V)(L) control system

With regular calibration, the calibration functions of the
HS5E(V)(L) control system make it possible to achieve consistent system
behavior by compensating long-term drifts.
You can only carry out the points below in conjunction with a pressure sensor.
Provision by customer or order of an HS5E(V)(L)
We recommend calibrating the HS5E(V)(L) control system in the following order:
1.
Calibration of pressure transducer 1 and 2 or A and B, if required
Calibration of the valve offset
2.
3.
Calibration of the swivel angle sensor's offset
4.
Calibration of the swivel angle sensor's gain
5.
Calibration of leakage compensation
You can find further information about configuring and controlling the
calibration functions in the functional description of the HydraulicDrive firmware
(data sheet 30330-RN).
Pressure command value
good control
Time
P
control system.