Controller Parameters (Parallel); Control Parameter Sets; Special Operating Modes - Bosch rexroth HS5E Instruction Manual

For axial piston variable pump a4vso, a4vbo, a4vsg and a4csg
Table of Contents

Advertisement

Starting up at zero pressure
open circuit
HS5E
Starting up at zero pressure
closed circuit
HS5E
Starting up at zero pressure
HS5EV
About this product | A4... with HS5E(V)(L) control system Series 1x and 30

5.3.3 Controller parameters (parallel)

The controller parameters below are involved in pressure and swivel angle control:
Table 6: Controller parameter
Description of the controller parameter
Pressure controller P-gain 1 positive
Pressure controller P-gain 1 negative
Pressure controller time constant D component positive
Pressure controller time constant D component negative
Pressure controller time constant swivel angle feedback
Gate time derivation actual pressure value 1
Gate time derivation actual pressure value 2
Swivel angle controller P-gain
Swivel angle controller time constant D component
p-point feedback time constant
p-point feedback filter time
After activation of the extended pressure controller with an inflected characteristic
curve, the additional controller parameters below are active:
Table 7: Controller parameter
Description of the controller parameter
Pressure controller P-gain 2 positive
Pressure controller P-gain 2 negative
Pressure controller deviation, positive threshold
Pressure controller deviation, negative threshold

5.3.4 Control parameter sets

For the HS5E(V)(L), you have the option of configuring and using up to four different
parameter sets. Using these parameter sets, it is possible to optimize the control
behavior of the HS5E(V)(L) to different connected oil volumes.

5.3.5 Special operating modes

In this chapter, we will describe specific applications. In these cases, the basic
operating modes are active (see page 24).
To start up the HS5E systems with an open circuit unit, it is not necessary to provide
hydraulic circuitry for classical depressurized start-up.
If no command values are specified for the pressure and swivel angle, virtually
load-free start-up is possible.
With a closed circuit unit, the swivel angle corresponding to the flow direction must
be preselected even if pressure control is run.
The HS5EV control system starts without load pressure with maximum swivel angle
(+100% V
). This may result in pressure peaks in the system until the system is
g max
adjusted.
Parameter number
P-0-2963
P-0-2964
P-0-2969
P-0-2970
P-0-2971
P-0-2960
P-0-2979
P-0-2977
P-0-2978
P-0-2974
P-0-2973
Parameter number
P-0-2965
P-0-2966
P-0-2967
P-0-2968
RE 92076-01-B/2021-04-22, Bosch Rexroth AG