Setting Controller Parameters - Bosch rexroth HS5E Instruction Manual

For axial piston variable pump a4vso, a4vbo, a4vsg and a4csg
Table of Contents

Advertisement

76/104
A4... with HS5E(V)(L) control system Series 1x and 30 | Commissioning
Bosch Rexroth AG, RE 92076-01-B/2021-04-22
Table 19: Errors and their remedy/cause
Fault
No voltage supply available Check voltage supply at the central plug of the electronics
Field bus does not work
Fault in the pressure
measurement branch
Fault in the swivel angle
measurement branch
Further explanations on the analysis of faults can be found in chapter 14
"Troubleshooting" on page 92.
1. Close all directional valves upstream of consumers.
2. Open directional valve to the oil reservoir for depressurized circulation.
3. Before activating the motor, feed forward low command values
(e.g. p = 15 bar, SW = 10%).
In this state, the HS5E pilot control valve reports an "error" (excessive control
difference). When the electronics is working properly, the fault message disappears
when the motor is switched on (control difference now equal to zero).
▶ Switching on the drive motor of the pump!

8.1.7 Setting controller parameters

The following description is to simplify setting of the controller parameters.
Depending on the application, you may not need to modify all of the parameters
listed here.
8.1.7.1 Setting controller parameters for cascade structure
Factory setting:
When the HS5E(V)(L) control system is delivered, controller parameters have already
been entered as the default value. This controller setting sets the controller to slow
behavior, which is stable with most systems.
To customize the controller to plant-specific requirements, you need to modify a few
parameters.
8.1.7.2 P-gain (proportional gain)
Table 20: P-gains
Parameters
P-0-2809
P-0-2977
These parameters are multiplied by the control difference of the respective
controller. This means that they have the effect of a linear gain factor in the
controller. The lower this value is set, the slower is the controller's response.
However, if you select a value that is too high, the system can become unstable.
When customizing the controller parameters to plant-specific behavior, you generally
only need to modify the P-gain in the pressure controller.
Remedy/cause
Check wiring
Check IP address
Read out the actual pressure value (p
output signal of the pressure transducer must match the type
of control electronics (current, voltage, nominal value).
Comparison of the actual swivel angle value (SW
visual indicator on the axial piston unit.
Designation
Pressure controller cascade P-gain
Swivel angle controller P-gain
); it must be 0 bar. The
actual
) with the
act

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rexroth hs5evRexroth hs5el

Table of Contents