CMS200
6.3.23 Defrost termination temperature (dtd)
Display
Description
Considerations
Range
Global default
6.3.24 Condenser high temperature (Ht)
Display
Description
Considerations
Range
Global default
6.3.25 Activity frequency (AF)
Display
Description
Considerations
Range
Global default
www.nexo.com
Defines the temperature to end the defrost cycle.
Ending defrost cycles on temperature minimizes the duration of defrost cycles.
• If icing up occurs, review the values of the defrost parameters.
-5 to 22ºC (23 to 72ºF)
15°C (59°F)
Defines the maximum temperature measured in the refrigeration system by
monitoring the condenser sensor.
On reaching the condenser high temperature (Ht), the controller disables the
compressor and activates an alarm.
• Requires a condenser sensor.
• To set the condenser high temperature (Ht), measure the refrigeration system
temperature when the condenser is 75% blocked.
• To disable, set below 50ºC or 122ºF.
0 to 125ºC (32 to 257ºF)
0ºC (32ºF) - disabled
Defines the minimum number of door openings or motion counts to indicate an active
30 minute period in the self-learning matrix, as described below.
See below.
See below.
0 (low frequency)